Trane Gas Furnace: TUD/TDD
Re: No Heat - Code 2
Code 2 = 3 Failed Ignition Attempts
Qty |
Possible Causes: |
1 |
Bad Glow Plug |
|
Dirty Flame Sensor |
|
Clogged Burners |
|
No or Low Gas Pressure |
|
Bad Gas Valve |
|
Bad Ignition Control |
CHECKOUT:
1. Check Ignition Sequence
- If the furnace is currently in lockout, reset by cycling power.
- Initiate a call for heat from the thermostat and monitor the ignition sequence.
- 1. The inducer motor should start with no difficulty.
- 2. The pressure switch should close within a couple seconds of the inducer starting.
- 3. The glow plug should energize within 30 seconds of the pressure switch closing.
- 4. The gas valve should open within 20 seconds of the glow plug energizing.
2. Check Ignition
- Visually inspect the burners during ignition.
- The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
3. Check Glow Plug
- Look for any visual cracks.
- Unplug the 2-wire connector to the glow plug.
- Use a meter to test resistance of the glow plug.
- No Resistance = Bad Glow Plug
- Start an ignition sequence.
- Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
- No Power = Bad Ignition Control
- Power Present but No Glow = Bad Glow Plug
► Replacement Glow Plug --> Use GLO.03 (025-32625-000)
4. Check Gas Pressure / Valve
- Inlet Gas Pressure
- Turn off power to the furnace and close the gas safety shut-off valve.
- Hook-up a gas pressure gauge to the inlet test port of the gas valve.
- Open the gas safety shut-off and check gas pressure.
- Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
- Low Pressure = Bad Meter or Regulator
- Re-apply power to the furnace and activate a call for heat.
- Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
- Pressure Drops Below Minimum = Bad Meter/Regulator or Restricted Gas Line
- Manifold Gas Pressure
- Turn off power to the furnace and close the gas safety shut-off.
- Move the gas pressure gauge to the manifold (leaving) test port on the gas valve.
- CAUTION! Be sure to put the plug back in the inlet test port before proceeding!
- Open the gas safety shut-off valve and re-apply furnace power.
- Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
- Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
- No Gas Pressure = Bad Gas Valve
- Low Gas Pressure --> Increase Manifold Gas Pressure
- Normal Gas Pressure but No or Delayed Ignition = Clogged Burners --> Remove burners and clean spreaders
5. Check Flame Sensor
- On the multi-meter:
- Switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Disconnect the wire from the flame sensor.
- Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
- Check the reading when the burners ignite.
- Normal Reading = 2 to 6 mA
- Minimum acceptable reading = 1 MicroAmp
- Low Reading = Dirty Flame Sensor --> Clean Flame Sensor & Re-check
- CAUTION! Move meter leads back to "COM" and "V" before proceeding!