Knowledgebase

YorkGuard VI Add-On Heat Pump Operation

Article ID: 119
Last updated: 22 Mar, 2017

York Heat Pumps: YorkGuard VI

Re: Add-On Heat Pump ("Fossil Fuel") Operation

When a heat pump equipped with a YorkGuard VI module is installed in an "Add-On" or "Fossil Fuel" application, the YorkGuard handles all of the "Fossil Fuel" sequences with the addition of a "Bonnet Sensor" between the gas furnace and indoor coil.

  • Configure the thermostat for standard Heat Pump operation.
  • No additional outdoor sensor required.
YorkGuard VI - "Fossil Fuel" Sequence of Operation

For Fossil Fuel Operation, the following setting must be made on the YorkGuard:

  • FFUEL = Set to "On"
  • BP = Set for 45, 40 or 35 deg.
  • LTCO = Set for 20, 15 or 10 deg.
  • Bonnet Sensor installed & wired to "BS" and "BSG"
1. Outdoor above Balance Point (BP)
  • On a call for "Y1" the YorkGuard energizes the compressor for 1st Stage heating.
  • On a call for "Y2" the YorkGuard energizes the compressor unloading solenoid to put the compressor in full operation.
    • The YorkGuard also energizes "Y2 Out" to tell the variable speed indoor fan to go to "High Heat" speed.
  • On a call for "W" (or "Aux") the YorkGuard will keep Aux Heat outputs "W1 Out" and "W2 Out" de-energized.
    • If the heat pump goes into a Lockout condition, the YorkGuard will automatically energize "W1 Out" to satisfy heating demand.
2. Outdoor below Balance Point (BP)
  • On a call for "Y1" the YorkGuard energizes the compressor for 1st Stage heating.
  • On a call for "Y2" the YorkGuard energizes the compressor unloading solenoid to put the compressor in full operation.
    • The YorkGuard also energizes "Y2 Out" to tell the variable speed indoor fan to go to "High Heat" speed.
  • On a call for "W" (or "Aux") the YorkGuard will energize "W1 Out" to start the furnace while keeping the compressor operating.
    • The compressor continues to operate until the Bonnet Sensor temperature reaches 90 deg.
      • If the furnace fails to operate the heat pump will continue to operate to try to maintain heating.
3. Outdoor below LTCO
  • The YorkGuard basically enters Emergency Heat mode.
  • On a call for "Y1" the YorkGuard keeps the compressor off and energizes "W1 Out" to start the gas furnace.

This article was:   Helpful | Not helpful
Report an issue
Article ID: 119
Last updated: 22 Mar, 2017
Revision: 6
Access: Public
Views: 139
Comments: 0
Also read

Also listed in