Last updated: 4 Dec, 2023
York Package Unit: PCG4 Re: Flashing Code 6 If, after the induced draft blower is energized, the pressure switch does not close, the control will keep the blower on and wait for the switch to close. The diagnostic code for this problem is 3 short flashes followed by a pause. Multiple Code 3's will cause a Code 6 Lockout.
CHECKOUT: 1. Check Control Board
4. Check Factory Restrictor Plate