PCG4 Flashing Code 6

York Package Unit: PCG4

Re: Flashing Code 6

If, after the induced draft blower is energized, the pressure switch does not close, the control will keep the blower on and wait for the switch to close. The diagnostic code for this problem is 3 short flashes followed by a pause.

Multiple Code 3's will cause a Code 6 Lockout.


Qty Possible Causes:
Bad Pressure Switch
3 Factory Restrictor Plate Issue
1 Bad Inducer Motor
1 Bad Inducer Motor Capacitor
Item Stuck in Pressure Port
Item Stuck in Inducer Motor
Bad Ignition Control


CHECKOUT:

1. Check Control Board


2. Check Inducer Motor


3. Check Pressure Switch


4. Check Factory Restrictor Plate



Article ID: 729
Last updated: 4 Dec, 2023
Revision: 1
Equipment -> Package Units -> York -> PCG4 -> PCG4 Flashing Code 6
https://ghac.makekb.com/entry/729/