Knowledgebase

PCG4 Flashing Code 4

Article ID: 707
Last updated: 30 Jan, 2023

York Package Unit: PCG4

Re: Flashing Code 4

Code 4 = Limit Switch or Roll-Out Switch Open

► The automatic-reset primary Limit Switch and the manual-reset Roll-Out Switch are wired in series, so either limit open will generate a Code 4.

NOTE: If the limit circuit remains open for more than 5 minutes, the control will switch to a Code 11

NOTE: If the limit circuit remains open for more than 15 minutes, the control assumes that a Roll-Out Switch has tripped and will switch to a Code 5


Qty Possible Causes:
Low Airflow
Bad Blower Motor
Excessive Gas Pressure
Bad Limit Switch
1 Tripped Roll-Out Switch
Bad Control Board


CHECKOUT:

1. Check the Limit Circuit

  • At the control board 9-pin plug, use a volt meter to check for 24VAC on each side of the limit circuit.
    • Check voltage between Pin#1 (Red/Grn 36) and "C".
    • Check voltage between Pin#5 (Red/Blk 35) and "C".
      • Power on One Side Only = Limit Circuit Open → Step 2. Check Limits
      • Power on Both Sides = Limit Circuit Closed ⇒ Reset the board by cycling power to the unit. 
        • Code 4 Returns + Limit Circuit Closed = Bad Control Board

2. Check Limits

  • Check the Roll-Out Limit
    • The Roll-Out Limit is located on the plate above the burners.
    • With the wires attached to the limit switch, check for 24VAC from each side of the Roll-Out Limit to "C".
      • Power on One Side Only = Limit Circuit Open → Article: PCG4 Flashing Code 5
      • Power on Both Sides = Limit Circuit Closed ⇒ Check the Primary Limit (below)
  • Check the Primary Limit
    • The Primary Limit is located inside the blower compartment and protrudes into the heat exchanger compartment.
    • With the wires attached to the limit switch, check for 24VAC from each side of the Limit Switch to "C".
      • Power on One Side Only = Limit Switch Open
        • Limit Switch Open + Hot Heat Chamber → Step 3. Check Blower
        • Limit Switch Open + Cool Heat Chamber = Bad Limit Switch
      • Power on Both Sides = Limit Switch Closed ⇒ Reset the board by cycling power to the unit. 
        • Code 4 Returns + Limit Circuit Closed = Bad Control Board

3. Check Blower

  • During a Code 4 lockout, the indoor blower should be running continuously.
  • Make sure that both the High Voltage and Low Voltage plug are secure at the ECM blower motor.
  • Check for 24VAC at the control board between "W SPD" and "24V COM".
    • ​​​​​​​Power Present + No Blower = Bad Blower Motor
    • No Power Present = Bad Control Board

4. Check Temperature Rise

  • Reset the control if necessary by cycling power to the unit.
  • Start the unit in a heat cycle.
  • Check the return air temperature in the blower door (don't assume that the house temperature = the return temperature).
  • Check the supply air temperature either in the ductwork near the unit or at a close supply vent.
    • Temperature Rise = Supply Air Temperature - Return Air Temperature
  • Compare the Actual Temperature Rise to the unit's Rated Temperature Rise (typically 40 - 70 deg).
    • ​​​​​​​Temperature Rise More than 70 deg → Step 5. Check Air Filter
    • Temperture Rise Less than deg + Code 4 ⇒ Suspect a Bad Limit Switch

5. Check Air Filter

  • Remove and inspect the air filter.
  • Recheck the temperature rise with the filter removed.
    • ​​​​​​​Temperature Rise Still High → Step 6. Check Gas Pressure
    • Temperature Rise Drops to Normal Range = Restricted Air Filter

6. Check Gas Pressure

  • Shut-off the unit by removing a call for "W".
  • Hook a gas pressure gauge to the outlet or "manifold" side of the gas valve.
  • Start a call for Heat and monitor the gas pressure when the unit fires.
    • Natural Gas = 2.5" w.c. minimum to 3.5" w.c. maximum
    • LP Gas = 9" w.c. minimum to 11" w.c. maximum
      • Pressure Below Maximum + High Temperature Rise → Step 7. Check Blower Speed
      • Pressure Above Maximum ⇒ Adjust Gas Pressure & Re-check Temperature Rise

7. Check Blower Speed

  • Shut-off the unit by removing a call for "W".
  • After the blower shuts off, remove high voltage power by pulling the service disconnect or turning the breaker off.
  • Check the Low Voltage plug at the ECM blower motor to see what speed the unit is using for Heat.
    • ​​​​​​​The White wire will be connected to one of the Low Voltage terminals of the motor (1=Low to 5=High).
    • If possible, move the White wire to a higher speed.
  • ​​​​​​​Re-apply power to the unit and energize a call for Heat.
  • Re-check the temperature rise.​​​​​​​
This article was:   Helpful | Not helpful
Report an issue
Article ID: 707
Last updated: 30 Jan, 2023
Revision: 10
Access: Public
Views: 119
Comments: 0