PCG4 Flashing Code 4

York Package Unit: PCG4

Re: Flashing Code 4

Code 4 = Limit Switch or Roll-Out Switch Open

► The automatic-reset primary Limit Switch and the manual-reset Roll-Out Switch are wired in series, so either limit open will generate a Code 4.

NOTE: If the limit circuit remains open for more than 5 minutes, the control will switch to a Code 11

NOTE: If the limit circuit remains open for more than 15 minutes, the control assumes that a Roll-Out Switch has tripped and will switch to a Code 5


Qty Possible Causes:
Low Airflow
Bad Blower Motor
Excessive Gas Pressure
Bad Limit Switch
1 Tripped Roll-Out Switch
Bad Control Board


CHECKOUT:

1. Check the Limit Circuit


2. Check Limits


3. Check Blower


4. Check Temperature Rise


5. Check Air Filter


6. Check Gas Pressure


7. Check Blower Speed