Knowledgebase

ZF120 - Heat Board - Code 3

Article ID: 686
Last updated: 4 Nov, 2021

York Rooftop Unit: ZF120

Re: Heat Board - Code 3

If, after the induced draft blower is energized, the pressure switch circuit does not close, the control will keep the blower on and wait for the switch to close. The diagnostic code for this problem is 3 short flashes followed by a pause.

► The diagnostic code will go away once the pressure switch closes.


Qty Possible Causes:
Bad Pressure Switch
Bad Inducer Motor
2 Clogged Pressure Nipple
Bad Ignition Control


CHECKOUT:

1. Check Control Board

  • Start the furnace with a call for heat.
    • Inducer motor should start within 15 seconds.

2. Check Inducer Motor

  • Start the furnace with a call for heat.
  • Observe and listen to inducer motor operation.
    • Inducer motor hums but does not start:
      • Bad Inducer Motor or Capacitor
      • Item in Inducer (Remove inducer & check)
  • Ensure that the pressure switch closes.

3. Check Pressure Switch

  • Use a pressure gauge to check the pressure at the switch while the inducer is running.
  • Compare actual pressure to pressure rating on the switch.
    • Pressure near or below rating:
      • Rusted Inducer Blower Wheel
      • Clogged Pressure Port
    • Pressure well above rating and switch doesn't close = Bad Switch
This article was:   Helpful | Not helpful
Report an issue
Article ID: 686
Last updated: 4 Nov, 2021
Revision: 6
Access: Public
Views: 36
Comments: 0