York Rooftop Unit: ZF

Re: Ignition Lockout Codes

Light Status Description
Off No Power
On Control Failure - Replace Control
Heartbeat Normal Operation - No faults
2 Flashes Pressure switch stuck closed
3 Flashes Pressure switch failed to close
4 Flashes Limit switch open
5 Flashes Flame present with no call for heat
6 Flashes Ignition failure
This article was:   Helpful | Not helpful