Flashing Code 10 = Compressors locked-out due to Low Ambient Temperature

If there is a call for Y1 and the LAS input is CLOSED, the control will lockout all compressors and flash a code 10.

► The LAS (Low Ambient Switch) is mounted to the unit base in the compressor compartment.


Qty Possible Causes:
1 Bad LAS (Low Ambient Switch)
1 Low Outdoor Air Temperature
Bad Control Board


CHECKOUT:

1. Check LAS

  • Remove the 6-wire (4-Black, 2-Blue) Plug from the control board.
  • Check resistance across the two bottom blue wires.
    • No Resistance = LAS Open
    • Resistance = LAS Closed
      • Closed + Warm Temp = Bad LAS 