York Rooftop Unit: DH, DM Re: Flashing Code 10 Flashing Code 10 = Compressors locked-out due to Low Ambient Temperature If there is a call for Y1 and the LAS input is CLOSED, the control will lockout all compressors and flash a code 10. ► The LAS (Low Ambient Switch) is mounted to the unit base in the compressor compartment.
CHECKOUT: 1. Check LAS