Predator - Flashing Code 10

York Rooftop Unit: DH, DM

Re: Flashing Code 10

Flashing Code 10 = Compressors locked-out due to Low Ambient Temperature

If there is a call for Y1 and the LAS input is CLOSED, the control will lockout all compressors and flash a code 10.

► The LAS (Low Ambient Switch) is mounted to the unit base in the compressor compartment.


Qty Possible Causes:
1 Bad LAS (Low Ambient Switch)
1 Low Outdoor Air Temperature
Bad Control Board


CHECKOUT:

1. Check LAS




Article ID: 559
Last updated: 14 Dec, 2018
Revision: 4
Equipment -> Rooftop Units -> York -> Predator DH, DM, -> Predator - Flashing Code 10
https://ghac.makekb.com/entry/559/