Knowledgebase

Ultra Series 2 - Burner Won't Stay Lit

Article ID: 55
Last updated: 30 Jan, 2017

Make:  Weil-Mclain

Model or Series:  Ultra 310

Type:  Boiler

Problem Description:  Low heat; Burners won't stay lit.

Observed Symptoms:  

  • Low water temperature.
  • Burners ignite normally.
  • Burner runs for several second, makes a vibrating noise then shuts off and shows code 6.
  • Burner retries automatically after about 1 minute and does the same thing.

Solution:  Replaced inducer assembly (P# 383-500-360) for $770.


Additional Information:  

  • Blower control board had signs of water damage.
  • Leaking unions on water piping running water into control cabinet and dripping on blower.
This article was:   Helpful | Not helpful
Report an issue
Article ID: 55
Last updated: 30 Jan, 2017
Revision: 5
Access: Public
Views: 362
Comments: 0