Knowledgebase

4WCC - Flashing Code 4 - Heating

Article ID: 517
Last updated: 15 Feb, 2018

Trane Package Heat Pump: 4WCC

Re: Heating - Flashing Code 4

Code 4 = 4 Low Pressure Switch openings 

► This is a Hard Lockout condition that must be reset by cycling power to the board.


Qty Possible Causes:
Low Refrigerant Charge
Bad O/D Expansion Valve
Bad I/D Expansion Valve
Bad Pressure Switch
?

CHECKOUT:

1. Check Refrigerant Pressures

  • Hook-up refrigerant gauges to the pressure ports on the unit (in the compressor section on the front-left corner of the unit).
    • Low Pressure = Loss of Charge
  • Reset the unit if necessary by cycling power to the unit.
  • Allow the unit to run for 5-10 minutes.
  • Monitor pressures as the system operates.
    • Normal R410a Heating Suction Pressure =  90 - 150 psig

2. Check Sub-Cooling

  • Sub-Cooling
  • Check the Liquid Line Temperature near the outdoor coil.
  • Record "Saturation Temperature" from the discharge pressure gauge.
    • Sub-Cooling = Saturation Temp - Liquid Line Temp
      • Normal Sub-Cooling = 3 - 12 deg.
  • Low Suction Pressure + High Sub-Cooling = Bad O/D Expansion Valve
  • Low Suction Pressure + Low Sub-Cooling = Low Refrigerant Charge 

3. Check Discharge Temperature

  • Connect a temperature thermistor to the compressor discharge line.
  • Allow the system to run for about 10 minutes and watch the actual discharge temperature.
    • Normal Discharge Temperature = 120 - 180 deg F.
    • High Discharge Temperature = Low Refrigerant Charge or Bad O/D Expansion Valve

4. Check Defrost

  • Run the unit through a defrost cycle by jumping the Test pins on the defrost board.
  • Monitor refrigerant suction pressure through a defrost cycle.
    • Normal Heating Pressure + Low Defrost Pressure = Bad I/D Expansion Valve

This article was:   Helpful | Not helpful
Report an issue
Article ID: 517
Last updated: 15 Feb, 2018
Revision: 4
Access: Public
Views: 139
Comments: 0