Lennox Rooftop Unit: GCS20
Re: Won't Come On / No Heat
This condition is generally reported two different ways by the customer:
- "The unit won't do anything." - Indicating that there is no activity from the furnace on a call for heat.
- "The unit makes a noise, but never blows-out hot air." - Indicating that the inducer motor runs, but ignition never takes place.
These units use a Johnson Controls "Direct Spark Ignition" controller.
- Once 24VAC is received between "Power" and "Ground", the control should start an ignition sequence.
- Generates Spark
- Opens Main Gas Valve
Diagnostic Light:
- Light On Continuous = Normal
- Flashing = Ignition Lockout
- Off = No Power or Faulty Control
Qty |
Possible Causes: |
|
Open Primary Limit |
|
Open Auxiliary Limit |
|
Open Roll-out Limit |
|
Pressure Switch Fault |
|
Ignition Control Locked-Out |
|
Bad Inducer Fan |
|
Bad Ignition Control |
1 |
Bad Thermostat (Thermostat not calling) |
CHECKOUT:
1. Check Power
- Check for 24VAC between "R" and "C" on the terminal block.
- No Power ⇒ Check High Voltage Power to the unit.
- High Voltage + No Low Voltage ⇒ Check the mini-breaker and transformer.
- Energize a call for Heat from the thermostat
- Check 24VAC between "W" and "C" on the terminal block.
- No Power = No Heat Call, check the thermostat.
- Ensure that the inducer motor starts.
- Inducer Running ⇒ Check for 24VAC between "Power" and "Ground" on the ignition control.
-
- No Inducer ⇒ Check for 230VAC going to the inducer.
- No Power = Bad K13 Inducer Relay
- Power Present + No Inducer Operation = Bad Inducer Motor
2. Check Safeties
- Primary Limit
- Check for 24VAC between the "C" and "N/C" wires of the limit to "C" on the terminal block.
- Power on one wire and not the other = Bad Limit or Limit Tripped
- Auxiliary Limit
- Check for 24VAC between the "C" and "N/C" wires of the limit to "C" on the terminal block.
- Power on one wire and not the other = Bad Limit or Limit Tripped
- Pressure Switch
- Check for 24VAC between both wires on the pressure switch & "C" on the terminal block.
- Power on one wire and not the other = Open Pressure Switch
- Roll-Out Limit
- Check for 24VAC between both sides of the limit and "C" on the terminal block.
- Power on one side and not the other = Limit Tripped ⇒ Push Reset button & Re-check
- If tripped, suspect a bad heat exchanger.
3. Check Ignition Control
- Look for a flashing lockout light on the control.
- Flashing Light = Lockout ⇒ Reset power and retry.
- The ignition control should begin sparking and the Gas Valve should energize within 15 seconds of receiving power.
- Spark + No Gas Valve → Step 4. Check Gas Valve
- No Spark + Gas Valve = Bad Ignition Control
- No Spark + No Gas Valve = Bad Ignition Control
4. Check Gas Valve
- At the point of ignition, check for 24VAC on the two wires feeding the gas valve.
- No Power = Bad Ignition Control
- Power + No Ignition ⇒ Check Inlet & Outlet Gas Pressure