Knowledgebase

GCS20 - No Heat/Won't Come On

Article ID: 461
Last updated: 18 Dec, 2017

Lennox Rooftop Unit: GCS20

Re: Won't Come On / No Heat

This condition is generally reported two different ways by the customer:

  1. "The unit won't do anything." - Indicating that there is no activity from the furnace on a call for heat.
  2. "The unit makes a noise, but never blows-out hot air." - Indicating that the inducer motor runs, but ignition never takes place.

These units use a Johnson Controls "Direct Spark Ignition" controller.

  • Once 24VAC is received between "Power" and "Ground", the control should start an ignition sequence.
    • Generates Spark
    • Opens Main Gas Valve

Diagnostic Light:

  • Light On Continuous = Normal
  • Flashing = Ignition Lockout
  • Off = No Power or Faulty Control

Qty Possible Causes:
Open Primary Limit
Open Auxiliary Limit
Open Roll-out Limit
Pressure Switch Fault
Ignition Control Locked-Out
Bad Inducer Fan
Bad Ignition Control
1 Bad Thermostat (Thermostat not calling)


CHECKOUT:

1. Check Power

  • Check for 24VAC between "R" and "C" on the terminal block.
    • No Power ⇒ Check High Voltage Power to the unit.
    • High Voltage + No Low Voltage ⇒ Check the mini-breaker and transformer.
  • Energize a call for Heat from the thermostat
  • Check 24VAC between "W" and "C" on the terminal block.
    • No Power = No Heat Call, check the thermostat.
  • Ensure that the inducer motor starts.
    • Inducer Running ⇒ Check for 24VAC between "Power" and "Ground" on the ignition control.
    • No Inducer ⇒ Check for 230VAC going to the inducer. 
      • No Power = Bad K13 Inducer Relay
      • Power Present + No Inducer Operation = Bad Inducer Motor

2. Check Safeties

  • Primary Limit
    • Check for 24VAC between the "C" and "N/C" wires of the limit to "C" on the terminal block.
      • Power on one wire and not the other = Bad Limit or Limit Tripped
  • Auxiliary Limit
    • Check for 24VAC between the "C" and "N/C" wires of the limit to "C" on the terminal block.
      • Power on one wire and not the other = Bad Limit or Limit Tripped
  • Pressure Switch
    • Check for 24VAC between both wires on the pressure switch & "C" on the terminal block.
      • Power on one wire and not the other = Open Pressure Switch
  • Roll-Out Limit
    • Check for 24VAC between both sides of the limit and "C" on the terminal block.
      • Power on one side and not the other = Limit Tripped ⇒ Push Reset button & Re-check
        • If tripped, suspect a bad heat exchanger.

3. Check Ignition Control

  • Look for a flashing lockout light on the control.
    • Flashing Light = Lockout ⇒ Reset power and retry.
  • The ignition control should begin sparking and the Gas Valve should energize within 15 seconds of receiving power.
    • Spark + No Gas Valve →  Step 4. Check Gas Valve
    • No Spark + Gas Valve = Bad Ignition Control
    • No Spark + No Gas Valve = Bad Ignition Control

4. Check Gas Valve

  • At the point of ignition, check for 24VAC on the two wires feeding the gas valve.
    • No Power = Bad Ignition Control
    • Power + No Ignition ⇒ Check Inlet & Outlet Gas Pressure
This article was:   Helpful | Not helpful
Report an issue
Article ID: 461
Last updated: 18 Dec, 2017
Revision: 5
Access: Public
Views: 58
Comments: 0