GCS20 - No Heat/Won't Come On

Lennox Rooftop Unit: GCS20

Re: Won't Come On / No Heat

This condition is generally reported two different ways by the customer:

  1. "The unit won't do anything." - Indicating that there is no activity from the furnace on a call for heat.
  2. "The unit makes a noise, but never blows-out hot air." - Indicating that the inducer motor runs, but ignition never takes place.

These units use a Johnson Controls "Direct Spark Ignition" controller.

Diagnostic Light:


Qty Possible Causes:
Open Primary Limit
Open Auxiliary Limit
Open Roll-out Limit
Pressure Switch Fault
Ignition Control Locked-Out
Bad Inducer Fan
Bad Ignition Control
1 Bad Thermostat (Thermostat not calling)


CHECKOUT:

1. Check Power


2. Check Safeties


3. Check Ignition Control


4. Check Gas Valve