Knowledgebase

4TTR - Cooling - Freezing-Up

Article ID: 323
Last updated: 21 Sep, 2017

Trane Air Conditioner: 4TTR

Re: Cooling Coil Freeze-Up

The indoor coil develops either a coating of thick, white frost or thick ice.

  • May only freeze a portion of the indoor coil or the entire coil.
  • Ice may extend from the indoor coil all the way to the compressor in the outdoor unit.
  • Generally causes a loss of airflow from the registers.

Qty Possible Causes:
1 Low Refrigerant Charge
Low/No Airflow
Bad Expansion Valve
Cold Outdoor Air
Cold Return Air

CHECKOUT:

1. Check Indoor Coil

  • DO NOT attempt to check the refrigerant charge with ice on the coil.
  • If possible, remove the coil access panel to check for ice.
  • If ice is still present, set the thermostat fan switch "On" and wait for the coil to thaw.

2. Check the Blower

  • Make sure that the fan motor is operating.
  • Check the blower wheel for correct rotation.
    • A blower wheel can be turning backwards and still blow air from the registers.

3. Check the Air Filter

  • Make sure the air filter is clean.
  • In some cases, it may not be possible to remove the filter until the coil thaws.
  • Be cautious of "Ultra Allergen" air filters - highly restrictive.

4. Check Refrigerant Charge

Normal Pressure Ranges
Refrigerant 55-75 Deg O/D 75-90 Deg O/D
R410A
  • 100-125 Suction
  • 250-320 Discharge
  • 120-140 Suction
  • 300-400 Discharge

Expansion Valve

Check Subcooling & Superheat

  • If a Liquid-Line Sight Glass is installed, observe for bubbles in the sight glass (after the system has been operating for at least 5 min.)
    • Low Subcooling = Bubbles in Sight Glass
    • High Subcooling = Clear Sight Glass
Suction Discharge Subcooling Superheat Cause
Low Low/Normal High Low Airflow/Heat Transfer
Low Low/Normal High High Bad Expansion Valve
Low Low Low High Low Refrigerant Charge

Fixed Orifice

Check Superheat

Suction Discharge Superheat Cause
Low Low High Low Refrigerant Charge
Low Low/Normal Low Airflow/Heat Transfer

5. Check Supply/Return Air Temperature

  • Check the Return Air Temperature at the furnace or air handler.
    • Minimum acceptable return air temperature = 64 deg.
  • Check the supply air temperature and calculate the coil temperature drop.
    • Normal Temperature Drop = 15 - 18 deg.
      • Low Temperature Drop = Low Refrigerant Charge or Bad Metering Device (Expansion Valve)
      • High Temperature Drop = Low Airflow
        • Dirty Air Filter
        • Dirty Coil
        • Dirty Blower Wheel
        • Low Blower Speed
        • Dirty Re-Coup Coil (90% furnaces)
        • Mis-Matched Equipment
This article was:   Helpful | Not helpful
Report an issue
Article ID: 323
Last updated: 21 Sep, 2017
Revision: 1
Access: Public
Views: 68
Comments: 0