4TTR - Cooling - Freezing-Up

Trane Air Conditioner: 4TTR

Re: Cooling Coil Freeze-Up

The indoor coil develops either a coating of thick, white frost or thick ice.


Qty Possible Causes:
1 Low Refrigerant Charge
Low/No Airflow
Bad Expansion Valve
Cold Outdoor Air
Cold Return Air

CHECKOUT:

1. Check Indoor Coil


2. Check the Blower


3. Check the Air Filter


4. Check Refrigerant Charge

Normal Pressure Ranges
Refrigerant 55-75 Deg O/D 75-90 Deg O/D
R410A
  • 100-125 Suction
  • 250-320 Discharge
  • 120-140 Suction
  • 300-400 Discharge

Expansion Valve

Check Subcooling & Superheat

Suction Discharge Subcooling Superheat Cause
Low Low/Normal High Low Airflow/Heat Transfer
Low Low/Normal High High Bad Expansion Valve
Low Low Low High Low Refrigerant Charge

Fixed Orifice

Check Superheat

Suction Discharge Superheat Cause
Low Low High Low Refrigerant Charge
Low Low/Normal Low Airflow/Heat Transfer

5. Check Supply/Return Air Temperature



Article ID: 323
Last updated: 21 Sep, 2017
Revision: 1
Equipment -> Air Conditioners -> Trane -> 4TTR -> 4TTR - Cooling - Freezing-Up