Knowledgebase

BP Lockout Codes

Article ID: 290
Last updated: 24 Apr, 2017

York Rooftop Unit: BP Series

Re: Lockout Codes

Light Status Description
On Steady Control Failure - Replace Control
1 Flash Not Applicable
2 Flashes Anti-Short-Cycle Delay
3 Flashes HPS1 Compressor Lockout
4 Flashes Not Applicable
5 Flashes LPS1 Compressor Lockout
6 Flashes Not Applicable
7 Flashes FS1 Compressor Lockout
8 Flashes Not Applicable
9 Flashes Ignition Control Lockout*
10 Flashes Compressor Locked-Out: Low Ambient
11 Flashes Compressor Locked-Out: Economizer
12 Flashes Blower Overload Relay Tripped
13 Flashes Compressor Locked-Out: Low Voltage
14 Flashes Eeprom Storage Failure
Off No Power or Control Failure

* See Ignition Control Board

This article was:   Helpful | Not helpful
Report an issue
Article ID: 290
Last updated: 24 Apr, 2017
Revision: 4
Access: Public
Views: 117
Comments: 0