York Rooftop Unit: BP Series
Re: Lockout Codes
Light Status | Description |
On Steady | Control Failure - Replace Control |
1 Flash | Not Applicable |
2 Flashes | Anti-Short-Cycle Delay |
3 Flashes | HPS1 Compressor Lockout |
4 Flashes | Not Applicable |
5 Flashes | LPS1 Compressor Lockout |
6 Flashes | Not Applicable |
7 Flashes | FS1 Compressor Lockout |
8 Flashes | Not Applicable |
9 Flashes | Ignition Control Lockout* |
10 Flashes | Compressor Locked-Out: Low Ambient |
11 Flashes | Compressor Locked-Out: Economizer |
12 Flashes | Blower Overload Relay Tripped |
13 Flashes | Compressor Locked-Out: Low Voltage |
14 Flashes | Eeprom Storage Failure |
Off | No Power or Control Failure |
* See Ignition Control Board