Package Unit: YCY_G
Re: Heating - Code 4
Code 4 = High Limit Switch Open
► The G-Series of the YCY package units utilize a Variable Speed Blower and an ICM Control Board.
Qty |
Possible Causes: |
1 |
Bad Blower Motor |
|
Bad ICM Control Board (ICM) |
|
Bad Ignition Control Board (ICB) |
|
Low Airflow |
|
Gas Over-Fired |
|
Bad Limit Switch |
CHECKOUT:
1. Check Blower Operation
- Make sure the thermostat is set correctly and calling for Heat.
- Check to see if sufficient air flow is coming from the supply registers.
2. Check Blower Motor
- If not already, set the thermostat Fan switch to the "On" position.
- Check for 24VAC power between "Gnd" and "G" on the ICM Board.
- No Power = No Call from the Thermostat
- Check the ICM Board for the Green "Fan" light.
- Power Present on "G" + No "Fan" Light = Bad ICM Board
- Check for 230V across the "Red" and "Black" wires of Fen Terminal Block (FTBA).
- 230V Present on FTBA + ICM "Fan" Light On + No Blower Operation = Bad Blower Motor
3. Check Ignition Control Board (ICB)
- Set the thermostat to call for heat.
- Check for 24VAC between "Gnd" and "R" on the ICB.
- No Power = No Power from Transformer
- Check for 24VAC between "Gnd" and "W1" on the ICB (1st Stage Heat).
- No Power on "W1" = No signal from thermostat
- Power on "W1" + ICB Flashing Code 4 = Limit Open (Fan outputs should be energized)
- Power on "W1" + ICB Fast Flash = Wait 30 seconds after burners ignite for fan outputs.
- Check for 24VAC between "Gnd" and "Indoor Blower Lo" on the ICB.
- Check for 24VAC between "Gnd" and "Indoor Blower Hi" on the ICB.
- 24V Power on "W1" + No Power on Indoor Blower "Hi" or "Lo" = Bad Ignition Control Board (ICB)
- 24V Power on Indoor Blower "Hi" or "Lo" + No Blower = Bad Blower Motor or Bad ICM Control Board
4. Check Limit Switch
- Set the thermostat to call for heat.
- Check for 24VAC between "Gnd" and "R" on the ICB.
- No Power = No Power from Transformer
- Check for 24VAC between "Gnd" and "W1" on the ICB (1st Stage Heat).
- No Power on "W1" = No signal from thermostat
- Power on "W1" + ICB Flashing Code 4 = Limit Open (Fan outputs should be energized)
- With the blower motor operating, check the discharge air temperature from the unit.
- Cool Air Temperature + Limit Still Open = Bad Limit Switch
- High Air Temperature --> Allow the furnace to cool (limit should reset).
5. Check Temperature Rise
- Set the thermostat to call for full heat.
- With the blower operating, check the return air temperature entering the unit.
- Check for 24VAC between "Gnd" and "W2" on the ICB.
- No Power = Thermostat not calling for 2nd Stage
- With the furnace operating in 'Full-Fire", check the supply air temperature leaving the unit.
- Compare the actual temperature rise with the nameplate rated temperature rise.
- Higher than Rated Temperature Rise = Low Airflow or Gas Over-Fired
- Lower than Rated Temperature Rise + Limit Opens = Bad Limit Switch