Knowledgebase

Trane Heat Pump - Kicking On and Off in Cooling

Article ID: 155
Last updated: 22 Sep, 2017

Trane Heat Pump: 4TWR

Re: Compressor Kicks On and Off in Cooling

The compressor and condenser fan motor cycle on and off rapidly.

  • Often accompanied by burnt compressor contactor points from excessive cycling.

► The Low and High Pressure switches are wired in series with the "Y" output from the defrost board to the compressor contactor.  A tripped switch will de-energize the contactor when it opens and re-energize once the switch closes. (No lockout)


Qty Possible Causes (From Most to Least Likely):
High Pressure - Overcharged
Low Pressure - Low Refrigerant Charge
High Pressure - Low Outdoor Airflow
Low Pressure - Low Indoor Airflow
Low Pressure - Bad Cooling Expansion Valve

CHECKOUT:

1. Check Refrigerant Pressures

  • Turn off power to the outdoor unit by pulling the service disconnect or turning off the breaker.
  • Hook-up refrigerant gauges to the pressure ports on the unit.
  • Re-apply power to the outdoor unit.
  • Start the compressor with a call for cooling from the thermostat.
    • Make sure the compressor and condenser fan start correctly.
      • Some units have a Fan-Cycling control that may delay the starting of the condenser fan.
      • No Fan Operation = Bad Condenser Motor/Capacitor or Bad Fan-Cycling Control
  • Observe refrigerant pressures as the system operates.

2. Check High Pressure Issues

  • If the Head Pressure exceeds Trip Point within 1 minute:
    • Suspect Bad Overcharge or No Outdoor Airflow
  • If the Head Pressure gradually climbs to Trip Point:
    • Place an insulated thermistor on the liquid line.
    • Calculate Sub-Cooling = (Liquid-Line Gauge Temperature - Actual Liquid-Line Temperature)
      • Sub-Cooling > 15 deg + High Head Pressure + High Suction Pressure = Overcharged
      • Sub-Cooling > 15 deg + High Head Pressure + Low Suction Pressure = Bad I/D Expansion Valve
      • Sub-Cooling < 2 deg + High Head Pressure + High Suction Pressure = Low Outdoor Airflow

3. Check Low Pressure Issues

  • If Suction Pressure drops below the Trip Point within 1 minute:
    • Attempt to add refrigerant to the system.
      • Suction Pressure + Head Pressure Climbs = Low Refrigerant
        • A Liquid Line Sight Glass should have bubbles until proper charge is achieved.
      • Head Pressure Climbs but Suction Pressure stays low or drops = Bad I/D Expansion Valve
        • A Liquid Line Sight Glass should be clear.
  • If Suction Pressure gradually drops to the Trip Point:
    • Place an insulated thermistor on the Suction Line.
    • Monitor the Suction Line Pressure and Temperature as the system operates.
      • Suction Pressure Drops + Suction Line Temperature Drops = Low Indoor Airflow
        • A Liquid Line Sight Glass should be clear.
        • The Suction Line may begin to freeze.
This article was:   Helpful | Not helpful
Report an issue
Article ID: 155
Last updated: 22 Sep, 2017
Revision: 13
Access: Public
Views: 801
Comments: 0