Knowledgebase

Trane Heat Pump - Kicking On and Off in Cooling

Article ID: 155
Last updated: 22 Sep, 2017

Trane Heat Pump: 4TWR

Re: Compressor Kicks On and Off in Cooling

The compressor and condenser fan motor cycle on and off rapidly.

  • Often accompanied by burnt compressor contactor points from excessive cycling.

The Low and High Pressure switches are wired in series with the "Y" output from the defrost board to the compressor contactor.  A tripped switch will de-energize the contactor when it opens and re-energize once the switch closes. (No lockout)


Qty Possible Causes (From Most to Least Likely):
High Pressure - Overcharged
Low Pressure - Low Refrigerant Charge
High Pressure - Low Outdoor Airflow
Low Pressure - Low Indoor Airflow
Low Pressure - Bad Cooling Expansion Valve

CHECKOUT:

1. Check Refrigerant Pressures

  • Turn off power to the outdoor unit by pulling the service disconnect or turning off the breaker.
  • Hook-up refrigerant gauges to the pressure ports on the unit.
  • Re-apply power to the outdoor unit.
  • Start the compressor with a call for cooling from the thermostat.
    • Make sure the compressor and condenser fan start correctly.
      • Some units have a Fan-Cycling control that may delay the starting of the condenser fan.
      • No Fan Operation = Bad Condenser Motor/Capacitor or Bad Fan-Cycling Control
  • Observe refrigerant pressures as the system operates.

2. Check High Pressure Issues

  • If the Head Pressure exceeds Trip Point within 1 minute:
    • Suspect Bad Overcharge or No Outdoor Airflow
  • If the Head Pressure gradually climbs to Trip Point:
    • Place an insulated thermistor on the liquid line.
    • Calculate Sub-Cooling = (Liquid-Line Gauge Temperature - Actual Liquid-Line Temperature)
      • Sub-Cooling > 15 deg + High Head Pressure + High Suction Pressure = Overcharged
      • Sub-Cooling > 15 deg + High Head Pressure + Low Suction Pressure = Bad I/D Expansion Valve
      • Sub-Cooling < 2 deg + High Head Pressure + High Suction Pressure = Low Outdoor Airflow

3. Check Low Pressure Issues

  • If Suction Pressure drops below the Trip Point within 1 minute:
    • Attempt to add refrigerant to the system.
      • Suction Pressure + Head Pressure Climbs = Low Refrigerant
        • A Liquid Line Sight Glass should have bubbles until proper charge is achieved.
      • Head Pressure Climbs but Suction Pressure stays low or drops = Bad I/D Expansion Valve
        • A Liquid Line Sight Glass should be clear.
  • If Suction Pressure gradually drops to the Trip Point:
    • Place an insulated thermistor on the Suction Line.
    • Monitor the Suction Line Pressure and Temperature as the system operates.
      • Suction Pressure Drops + Suction Line Temperature Drops = Low Indoor Airflow
        • A Liquid Line Sight Glass should be clear.
        • The Suction Line may begin to freeze.
This article was:   Helpful | Not helpful
Report an issue
Article ID: 155
Last updated: 22 Sep, 2017
Revision: 13
Access: Public
Views: 450
Comments: 0