Knowledgebase

Sanyo VRF - Error Code E04

Article ID: 148
Last updated: 16 Jan, 2017

Sanyo Variable Refrigerant Flow

Re: Error Code E04 / Fault Code E04

Error Code E04 = Number of detected indoor units does not match the quantity of indoor units set on the outdoor unit control board.


Possible Causes (From Most to Least Likely):

  1. Indoor Unit(s) Powered Off
  2. Break in Communication Wire
  3. Incorrect ID Unit Setting

CHECKOUT

  1. Confirm Error Code
    • Check LED1 & LED2 on the outdoor unit control board.
      • LED1 Flashes: 2=P Alarm, 3=H Alarm, 4=E Alarm, 5=F Alarm, 6=L Alarm
      • LED2 Flashes = Alarm No.
        • LED1 Flashes 4, LED2 Flashes 4 = "E04"
  2. Check each indoor unit on the system to make sure that it has power.
This article was:   Helpful | Not helpful
Report an issue
Article ID: 148
Last updated: 16 Jan, 2017
Revision: 3
Access: Public
Views: 6268
Comments: 0