Goodman GPG Fault Codes
Goodman Package Units: GPG13 & 14 Re: Lockout Codes Red Light Description Off No Power or Faulty control On Power On 1 Ignition Failure, Open Rollout or Open Aux Limit 2 Pressure switch failed to close 3 Pressure switch failed to open (stuck...
21 Mar, 2017 Comments: 0
GPG13 - Flashing Code 1
​Goodman Package Unit: GPG13 Re: Flashing Code 1 / Won't Ignite Code 1 = 3 Failed Ignition Attempts ► A Manual-Reset Auxiliary Limit and Roll-Out Limit are wired in series with the gas valve and will cause a Fault Code 1. Qty Possible Causes: Dirty Flame Sensor Bad...
19 Dec, 2023 Comments: 0
GPG13 - Flashing Code 3
Goodman Package Unit: GPG13 Re: Flashing Code 3 Code 3 = Pressure switch failed to open (stuck closed) The furnace pressure switch should only close when the inducer fan output is energized. If control board is not energizing the inducer fan output and the switch is closed, the board will...
18 Jan, 2022 Comments: 0
GPG13 Low On Refrigerant
Goodman Package Unit: GPG13 Re: Low on Refrigerant / Freon A package unit that is low on refrigerant indicates a refrigerant leak. Qty Possible Causes (From Most to Least Likely): 1 Leaking Indoor Coil Leaking Outdoor Coil Leaking Schrader Other...
22 Sep, 2017 Comments: 0
Goodman GPG13 - Flashing Code 4
Goodman Package Unit: GPG13 Re: Flashing Code 4 If the limit control opens, the burners will be de-energized and the air circulation and vent blower will be powered until the limit closes. The diagnostic light code for this is four short flashes followed by a pause. ► The diagnostic code...