RPNL - Outdoor Fan Not Working

Article ID: 610
Last updated: 16 Mar, 2021

Rheem Heat Pump: RPNL / RPQL

Re: Outdoor Fan Not Working

These heat pump models have a control board which directly controls compressor and outdoor fan operation (no contactor).

In the Cooling Mode, this condition should cause a Code 23: Hi Pressure Fault

In the Heating Mode, this condition may cause a Code 21: Low Pressure Fault


Qty Possible Causes:
2 Bad Control Board
1 Bad Fan Motor
Bad Capacitor

CHECKOUT:

1. Check Motor Power

  • With the unit calling for compressor operation, check for 230V between E8 (CAP COM) and E16 (FAN RUN) on the control board.

2. Check Capacitor

  • Disconnect Power to the Outdoor Unit!
  • Remove the Orange wire from the FAN terminal of the capacitor.
  • Use a multi-meter to test the capacitor.
    • Good Capacitor + No Fan Operation = Bad Fan Motor 

3. Bad Control Board - Temporary Workaround

  • Disconnect Power to the Outdoor Unit!
  • Place a Double-Spade adapter on the E17 (START RLY) terminal.
  • Run an extra wire between E17 (START RLY) and one of the open defrost board FAN terminals.
  • Move the Black fan motor wire from E16 (FAN RUN) to the other open defrost board FAN terminal.
  • This should cause the fan to run when the compressor is on and shut off during defrost until the main control board is replaced.