Heat Pump: GSH13
Re: Making Humming Noise
When the unit is operating in heating or cooling it makes a loud humming noise.
Qty |
Possible Causes: |
1 |
Bad Capacitor |
1 |
Locked-Up Compressor |
|
Bad Fan Motor |
|
Low Line Voltage |
|
Burnt Wires |
|
Bad Contactor |
|
Defrost Mode |
CHECKOUT:
1. Check Power
- Disconnect power to the outdoor unit by pulling the service disconnect.
- Remove the outdoor unit electrical access panel.
- Look for any signs of burnt wires or controls.
- Re-apply power to the unit by re-inserting the service disconnect plug.
- Check for 230VAC power entering the contactor.
2. Check Capacitor
- Remove power to the unit by pulling the service disconnect.
- Discharge the capacitor by shorting the terminals with a screw driver.
- Compressor
- At the capacitor, remove the wires attached to "C" and "HERM".
- Move Multi-Meter leads to COM and MFD.
- Set Meter to 200 MFD.
- Place one meter lead on "C" and the other on "HERM".
- Confirm MFD reading with capacitor rating.
- Less than 80% of rating = Bad Capacitor
- Fan
- At the capacitor, remove the wires attached to "C" and "FAN".
- Place one meter lead on "C" and the other on "FAN".
- Confirm MFD reading with capacitor rating.
- Less than 80% of rating = Bad Capacitor
- SWITCH METER LEADS BACK TO COM AND V BEFORE PROCEEDING!
3. Check Unit Operation
- Attach an Amp Probe to one of the inlet power wires.
- Re-apply power to the unit.
- If necessary, energize the contactor by setting the thermostat to call for either heating or cooling (or manually push-in the contactor).
- Watch unit amperage and confirm that the compressor and condenser fan start.
- Excessive Amperage → Step 4. Check Compressor
- Outdoor Fan Doesn't Start ⇒ Check outlet voltage at contactor with contactor energized.
- No or Low Voltage = Bad Contactor
4. Check Compressor
- Remove power from the unit by pulling the service disconnect.
- Remove the compressor "Common" wire, either at the contactor or at the compressor.
- Check resistance of the compressor windings from "Common" to "Start" and "Common" to "Run".
- Resistance Between Each Winding + Excessive Start Amperage ⇒ Install a Hard Start and Re-check amperage.
- Still Won't Start/Excessive Amperage = Locked-Up Comnpressor
- No Resistance on Either Winding = Burnt Compressor Terminal or Open Compressor Windings
5. Check Condenser Fan
- Manually spin the condenser fan blade.
- Won't Spin/Difficult to Spin = Bad Fan Motor ⇒ Check to see if motor has oil ports.
- Turns Freely + Won't start ⇒ Check voltage to the motor with contactor energized.
- No Power = Bad Contactor or In Defrost Mode
- Power + No Operation = Bad Fan Motor