Knowledgebase

YCH - Ignition Control Faults

Article ID: 447
Last updated: 5 Dec, 2017

Trane Package Unit: YCH

Re: Ignition Lockout Codes

Trane YCH package units are multi-stage gas/electric units.

  • These units have a separate ignition control board which controls all heating functions except the indoor blower.
  • The ICB has a diagnostic light to indicate heat status.

Light Status Description
OFF No Power/Internal Failure
ON Normal/No Call for Heat
Pulse Normal/Call for Heat
1 Communication Loss
2 Lockout - No Flame Sensed (3 tries)
4 High Limit (TCO) Open
5 Flame Sensed with Gas Valve Off
This article was:   Helpful | Not helpful
Report an issue
Article ID: 447
Last updated: 5 Dec, 2017
Revision: 7
Access: Public
Views: 46
Comments: 0