Knowledgebase

AOU24RLXFZ Refrigerant Charge

Article ID: 434
Last updated: 21 Nov, 2017

Fujitsu Mini-Split: AOU24RLXFZ

Re: Refrigerant Charge

Refrigerant Type R410a
Pre-Charge Amount 4lbs - 14oz.
98 ft. Full Charge 4lbs - 14oz.
131 ft. Full Charge 5lbs - 5oz.
164 ft. Full Charge 5lbs - 12oz.
Maximum Total Pipe Length 164 ft.
Minimum Total Pipe Length 49 ft.
Maximum Unit Pipe Length 82 ft.
Minimum Unit Pipe Length 16 ft.
Maximum Elevation 49 ft.

This article was:   Helpful | Not helpful