Knowledgebase

DNH - Pilot Lights but Burners Won't Ignite

Article ID: 375
Last updated: 30 Jan, 2023

York Package Units: DNH

Re: Pilot Lights but Burners Won't Ignite

These package gas/electric units use a Honeywell Smart Valve for ignition.

  • Sequence Of Operation
  • On a call for heat, the fan timer board starts the inducer fan motor and sends 24V through the pressure switch to the Smart Valve.
  • When the Smart Valve receives a demand for heat it powers the 24V glow plug and opens the pilot valve.
  • When a pilot flame is sensed, the Smart Valve opens the main valve to allow gas flow to the burners.

Qty Possible Causes:
1 Bad Gas Valve
Dirty Flame Sensor
1 Clogged Pilot Orifice
Clogged Burners

CHECKOUT:

1. Check Pilot Flame


2. Check Gas Pressure

  • Disconnect line voltage power from the unit.
  • Shut the gas safety shut-off valve to the unit.
  • Hook-up a gas pressure gauge to the inlet gas pressure port.
  • Open the gas safety shut-off valve & monitor inlet gas pressure.
    • No or Very Low Pressure = Gas Supply Issue
  • Re-apply power to the unit.
  • Energize a call for heat.
  • Monitor inlet pressure while the glow plug energizes.

3. Check Pilot Orifice

  • Disconnect the aluminum pilot tubing from the gas valve.
  • Energize a call for heat.
  • Ensure that gas comes out of the pilot gas port.
    • No Pilot Gas = Bad Smart Valve
    • Pilot Gas Present ⇒ Disconnect and blow through the pilot tubing to see if the pilot orifice is clear.
      • Pilot Orifice Clear ⇒ Increase Pilot Gas Pressure

4. Check Flame Sensor

  • Disconnect the pilot tubing from the gas valve (if not already disconnected).
  • Remove the two screws that mount the pilot assembly to the burner manifold.
  • Carefully remove the pilot assembly along with the pilot tubing.
  • Clean the flame sensor. BE CAREFUL NOT TO BREAK THE GLOW PLUG!
  • Re-install the pilot assembly and re-connect the pilot tubing.
  • Energize a call for heat.
  • Ensure that the pilot lights and the main burners ignite.
    • Pilot + No Main Gas = Bad Smart Valve
    • Pilot + Main Gas + No Main Flame = Clogged Burners ⇒ Remove burners and clean burner wings.
This article was:   Helpful | Not helpful