Trane Reliatel - Won't Go Into Test Mode

Article ID: 217
Last updated: 9 Feb, 2017

Trane Reliatel Rooftop Units 

Re: Won't Go Into Test Mode

Trane Reliatel rooftop units have a Test mode that will cycle the unit through each connected operational function.

Each step of unit operation can be activated individually by temporarily shorting across the “Test” terminals for two to three seconds.

  • The Liteport LED located on the RTRM module will begin blinking when the test mode has been initiated.
  • The unit can be left in any “Test” step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch.
  • Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the “System” control.

Qty Likely Causes of Code 1 (from most to least likely):
1 Em Stop Circuit Open
Bad Reliatel (RTRM) Board