Trane Air Handler: GAM5

Re: Status Codes / Error Codes / Fault Codes

EVC STATUS LED
Flash Description
1 Cool Mode - No Active Call
3 Cool Mode - Active Call for Cooling or Defrost
4 Heat Mode or Off - No Active Call
6 Heat Mode - Active Call for Heating

EVC FAULT CODES
Flash Description
1 Stepper motor coil is open or has intermittent short
2 Control has detected an internal fault
3 Evaporator temperature sensor out of range
4 Gas temperature sensor out of range
5 Stepper motor coil is shorted
6 Valve is not responding to a change in position
7 High superheat
10 Low superheat
11 Condensate overflow switch activated for 100 sec.
13 Indoor frost protection activated