Knowledgebase

Heat Control Board Flashing Code 1

Article ID: 107
Last updated: 6 Feb, 2017

Trane Reliatel Rooftop Units 

Re: Heat Fault Code 1

Reliatel gas/electric rooftop units have a Heat Control Board as well as the Reliatel Control Board.

There are several version of the Heat Control Board, but two main varieties: 1) Spark ignition and 2) Hot Surface ignition.

The Heat Control Board has an LED for displaying status & fault information. It is very common for the heat faults to not be shown anywhere on the Trane diagrams.


Code 1 = Communication Fault

The Heat Control Board uses Modbus communications to communicate with the Reliatel Control Board. A Code 1 indicates a loss of communications between the two.


Qty Likely Causes of Code 1 (from most to least likely):
1 Bad Reliatel (RTRM) Board
Bad Heat Control Board
Bad wiring between RTRM & Heat Control Board

This article was:   Helpful | Not helpful
Report an issue
Article ID: 107
Last updated: 6 Feb, 2017
Revision: 8
Access: Public
Views: 40
Comments: 0
Also read