Configure 2-Stage Geothermal

Article ID: 73
Last updated: 5 Jul, 2018

Honeywell Thermostats: TH8320R & TH8321R

Re: Configure the thermostat for a 2-Stage Geothermal

Step 1: Go to "Installer Setup"

  • From the HOME Screen press the MENU tab
  • Scroll down and select "Installer Options"
  • Enter Factory Password
  • Select "Installer Setup"

Step 2: Enter Setup Information below:

Setup# Description Option
101 APPLICATION "residential" or "commercial"
103 THERMOSTAT NAME Select Appropriate Name
104 THERMOSTAT TYPE "programmable"
105 TEMPERATURE SCALE "farenheit"
106 OUTDOOR AIR SENSOR Optional
200 HEATING SYSTEM "heat pump"
201 HEATING EQUIPMENT "geothermal"
206 REVERSING VALVE "o (o/b on cool)"
207 COMPRESSOR STAGES 2
207 BACKUP HEAT STAGES 1
218 BACKUP HEAT TYPE "electric"
300 SYSTEM CHANGEOVER "automatic"
300 AUTO CHANGE DEADBAND 3
301 CONTROL OPTIONS "advanced options"
302 FINISH WITH HIGH COOL No
302 FINISH WITH HIGH HEAT No
303 COOL DIFFERENTIAL STAGE 2 2.0
306 COMP. HEAT DIFF. STAGE 2 "comfort'
309 BACKUP HEAT DROOP 2.0
311 UPSTAGE TIMER FOR BACKUP Off
312 OUTDOOR LOCKOUT H/P Off
312 O/D LOCKOUT BACKUP HEAT Off
314 COMP CYCLES PER HR STAGE 1 3
314 COMP CYCLES PER HH STAGE 2 3
316 BACKUP HEAT CYCLES PER HR 9
324 COMPRESSOR OFF TIME 3 minutes
326 EXTENDED FAN RUN IN COOL Off
326 EXTENDED FAN RUN IN HEAT Off
400 SCHEDULE PERIODS "4 periods per day"
409 ADAPTIVE RECOVERY Yes
410 MINIMUM COOL SETPOINT 64 deg
410 MAXIMUM HEAT SETPOINT 82 deg
411 KEYPAD LOCKOUT "Unlocked"
500 WIRED SENSOR ON S TERMINAL No
700 FILTER TYPE "media"
702 NUMBER OF AIR FILTERS 1
711 AIR FILTER "reminder-off"
800* HUMIDIFIER TYPE "none" or "bypass-fan/pwrd"
803* HUMIDIFIER WIRING "t-stat terminal U1"
805* WINDOW PROTECTION Off
806* USE HIMIDIFIER IN HEAT MODE Yes
806* USE HUMIDIFIER IN OFF MODE No
807* HUMIDIFIER CONTROL "hum when heat is on"
810 HUMIDIFIER PAD "reminder-off"
900* DEHUM EQUIPMENT "A/C with high fan"
907* DEHUM OVER COOLING LIMIT 1 deg
918* DEHUM AWAY MODE "not allowed"
921* DEHUMIDIFIER FILTER "reminder-off"
1000 VENTILATION TYPE "none"
1017 VENTILATION FILTER "reminder-off"
1100 NUMBER OF UV DEVICES 0
1105 UV BULB "reminder-off"
1200 CUSTOM REMINDERS
28 BACKLIGHTING "continuous"
1400 CLOCK FORMAT "12 hour"
1401 DAYLIGHT SAVING TIME On
1402 INDOOR TEMPERATURE OFFSET 0 deg
1404 ALERT LIGHT INDICATOR On
1500 DEALER NAME "GHAC, INC"
1500 DEALER PHONE 606-836-8143
1501 DEALER EMAIL service@ghacinc.com
1501 DEALER WEBSITE www.ghacinc.com
1502 DEALER MESSAGE

* = TH8321R Options Only

Step 3: Press "Done"

  • "Do you want to exit Installer Setup? Press "Yes"
  • "Do you want to save changes?" Press "Yes"

Step 4: Press "HOME" to go back to the Home Screen.