Honeywell Thermostats: TH8320R & TH8321R
Re: Configure the thermostat for a 2-Stage Geothermal
Step 1: Go to "Installer Setup"
Step 2: Enter Setup Information below:
Setup# | Description | Option |
101 | APPLICATION | "residential" or "commercial" |
103 | THERMOSTAT NAME | Select Appropriate Name |
104 | THERMOSTAT TYPE | "programmable" |
105 | TEMPERATURE SCALE | "farenheit" |
106 | OUTDOOR AIR SENSOR | Optional |
200 | HEATING SYSTEM | "heat pump" |
201 | HEATING EQUIPMENT | "geothermal" |
206 | REVERSING VALVE | "o (o/b on cool)" |
207 | COMPRESSOR STAGES | 2 |
207 | BACKUP HEAT STAGES | 1 |
218 | BACKUP HEAT TYPE | "electric" |
300 | SYSTEM CHANGEOVER | "automatic" |
300 | AUTO CHANGE DEADBAND | 3 |
301 | CONTROL OPTIONS | "advanced options" |
302 | FINISH WITH HIGH COOL | No |
302 | FINISH WITH HIGH HEAT | No |
303 | COOL DIFFERENTIAL STAGE 2 | 2.0 |
306 | COMP. HEAT DIFF. STAGE 2 | "comfort' |
309 | BACKUP HEAT DROOP | 2.0 |
311 | UPSTAGE TIMER FOR BACKUP | Off |
312 | OUTDOOR LOCKOUT H/P | Off |
312 | O/D LOCKOUT BACKUP HEAT | Off |
314 | COMP CYCLES PER HR STAGE 1 | 3 |
314 | COMP CYCLES PER HH STAGE 2 | 3 |
316 | BACKUP HEAT CYCLES PER HR | 9 |
324 | COMPRESSOR OFF TIME | 3 minutes |
326 | EXTENDED FAN RUN IN COOL | Off |
326 | EXTENDED FAN RUN IN HEAT | Off |
400 | SCHEDULE PERIODS | "4 periods per day" |
409 | ADAPTIVE RECOVERY | Yes |
410 | MINIMUM COOL SETPOINT | 64 deg |
410 | MAXIMUM HEAT SETPOINT | 82 deg |
411 | KEYPAD LOCKOUT | "Unlocked" |
500 | WIRED SENSOR ON S TERMINAL | No |
700 | FILTER TYPE | "media" |
702 | NUMBER OF AIR FILTERS | 1 |
711 | AIR FILTER | "reminder-off" |
800* | HUMIDIFIER TYPE | "none" or "bypass-fan/pwrd" |
803* | HUMIDIFIER WIRING | "t-stat terminal U1" |
805* | WINDOW PROTECTION | Off |
806* | USE HIMIDIFIER IN HEAT MODE | Yes |
806* | USE HUMIDIFIER IN OFF MODE | No |
807* | HUMIDIFIER CONTROL | "hum when heat is on" |
810 | HUMIDIFIER PAD | "reminder-off" |
900* | DEHUM EQUIPMENT | "A/C with high fan" |
907* | DEHUM OVER COOLING LIMIT | 1 deg |
918* | DEHUM AWAY MODE | "not allowed" |
921* | DEHUMIDIFIER FILTER | "reminder-off" |
1000 | VENTILATION TYPE | "none" |
1017 | VENTILATION FILTER | "reminder-off" |
1100 | NUMBER OF UV DEVICES | 0 |
1105 | UV BULB | "reminder-off" |
1200 | CUSTOM REMINDERS | |
28 | BACKLIGHTING | "continuous" |
1400 | CLOCK FORMAT | "12 hour" |
1401 | DAYLIGHT SAVING TIME | On |
1402 | INDOOR TEMPERATURE OFFSET | 0 deg |
1404 | ALERT LIGHT INDICATOR | On |
1500 | DEALER NAME | "GHAC, INC" |
1500 | DEALER PHONE | 606-836-8143 |
1501 | DEALER EMAIL | service@ghacinc.com |
1501 | DEALER WEBSITE | www.ghacinc.com |
1502 | DEALER MESSAGE |
* = TH8321R Options Only
Step 3: Press "Done"
Step 4: Press "HOME" to go back to the Home Screen.