Honeywell Thermostats: TH8320R & TH8321R
Re: Configure the thermostat for a 1-Stage Add-On Heat Pump
Step 1: Go to "Installer Setup"
- From the HOME Screen press the MENU tab
- Scroll down and select "Installer Options"
- Enter the Factory Password
- Select "Installer Setup"
Step 2: Enter Setup Information below:
| Setup# |
Description |
Option |
| 101 |
APPLICATION |
"residential" or "commercial" |
| 103 |
THERMOSTAT NAME |
Select Appropriate Name |
| 104 |
THERMOSTAT TYPE |
"programmable" (optional) |
| 105 |
TEMPERATURE SCALE |
"farenheit" |
| 106 |
OUTDOOR AIR SENSOR |
"Yes" |
| 200 |
HEATING SYSTEM |
"heat pump" |
| 201 |
HEATING EQUIPMENT |
"air to air heat pump" |
| 206 |
REVERSING VALVE |
"o (o/b on cool)" |
| 207 |
COMPRESSOR STAGES |
1 |
| 207 |
BACKUP HEAT STAGES |
1 |
| 218 |
BACKUP HEAT TYPE |
"Gas/Oil" |
| 219 |
EXTERNAL FOSSIL FUEL KIT |
"No" |
| 300 |
SYSTEM CHANGEOVER |
"automatic" |
| 300 |
AUTO CHANGE DEADBAND |
3 |
| 301 |
CONTROL OPTIONS |
"advanced options" |
| 302 |
FINISH WITH HIGH HEAT |
"Yes" |
| 309 |
BACKUP HEAT DROOP |
2.0 |
| 311 |
UPSTAGE TIMER BACKUP HT |
Off |
| 312 |
OUTDOOR LOCKOUT H/P |
40 Deg |
| 312 (a) |
O/D LOCKOUT BACKUP HEAT |
Off |
| 314 |
COMPRESSOR CYCLES STG 1 |
3 |
| 316 |
BACKUP HEAT CYCLES PER HR |
5 |
| 324 |
COMPRESSOR OFF TIME |
3 minutes |
| 326 |
EXTENDED FAN RUN IN COOL |
Off |
| 326 |
EXTENDED FAN RUN IN HEAT |
Off |
| 400 |
SCHEDULE PERIODS |
"4 periods per day" |
| 401 |
PRE-OCCUPANCY PURGE |
Off |
| 402 |
TYPE OF OVERRIDE |
standard |
| 403 |
OVERRIDE DURRATION |
4 hours |
| 405 |
MIN HEAT RECOVERY RATE |
3º/hr |
| 407 |
MIN COOL RECOVERY RATE |
5º/hr |
| 409 |
ADAPTIVE RECOVERY |
Yes |
| 410 |
MINIMUM COOL SETPOINT |
64 deg |
| 410 |
MAXIMUM HEAT SETPOINT |
82 deg |
| 411 |
KEYPAD LOCKOUT |
"Unlocked" |
| 500 |
WIRED SENSOR ON S TERMINAL |
Yes |
| 500 (a) |
WIRED INDOOR SENSOR |
No |
| 500 (b) |
WIRED OUTDOOR SENSOR |
Yes |
| 500 (c) |
WIRED DISCHARGE AIR SENSOR |
No |
| 505 |
O/D SENSOR TERMINAL S1 |
<Next> |
| 700 |
FILTER TYPE |
"media" |
| 702 |
NUMBER OF AIR FILTERS |
1 |
| 711 |
AIR FILTER |
"reminder-off" |
| 800 |
HUMIDIFIER TYPE |
"none" or "bypass-fan/pwrd" |
| 803 |
HUMIDIFIER WIRING |
"t-stat terminal U1" |
| 805 |
WINDOW PROTECTION |
Off |
| 806 |
USE HIMIDIFIER IN HEAT MODE |
Yes |
| 806 |
USE HUMIDIFIER IN OFF MODE |
No |
| 807 |
HUMIDIFIER CONTROL |
"hum when heat is on" |
| 810 |
HUMIDIFIER PAD |
"reminder-off" |
| 900 |
DEHUM EQUIPMENT |
"A/C with high fan" |
| 907 |
DEHUM OVER COOLING LIMIT |
1 deg |
| 918 |
DEHUM AWAY MODE |
"not allowed" |
| 921 |
DEHUMIDIFIER FILTER |
"reminder-off" |
| 1000 |
VENTILATION TYPE |
"none" |
| 1017 |
VENTILATION FILTER |
"reminder-off" |
| 1100 |
NUMBER OF UV DEVICES |
0 |
| 1200 |
CUSTOM REMINDERS |
|
| 28 |
BACKLIGHTING |
"continuous" |
| 1400 |
CLOCK FORMAT |
"12 hour" |
| 1401 |
DAYLIGHT SAVING TIME |
On |
| 1402 |
INDOOR TEMPERATURE OFFSET |
0 deg |
| 1402 |
SHOW HUMIDITY |
Yes |
| 1402 |
INDOOR HUMIDITY OFFSET |
0% |
| 1404 |
ALERT LIGHT INDICATOR |
On |
| 1500 |
DEALER NAME |
"GHAC, INC" |
| 1500 |
DEALER PHONE |
606-836-8143 |
| 1501 |
DEALER EMAIL |
service@ghacinc.com |
| 1501 |
DEALER WEBSITE |
www.ghacinc.com |
| 1502 |
DEALER MESSAGE |
|
- TH8321R (Humidity) Options Only
- Commercial Options Only
Step 3: Press "Done"
- "Do you want to exit Installer Setup? Press "Yes"
- "Do you want to save changes?" Press "Yes"
Step 4: Press "HOME" to go back to the Home Screen.
WIRING
| Thermostat |
Furnace |
Heat Pump |
| R |
R |
R |
| C |
C |
C |
| G |
G |
|
| W/Aux |
W |
W, W1, or X (Trane) |
| Y |
Y or Y/Y2 |
Y |
| O |
(wire nut) |
O |
| S1* |
(wire nut) |
O/D Sensor 1 |
| S1* |
(wire nut) |
O/D Sensor 2 |
* If using a wired outdoor air sensor.
SEQUENCE OF OPERATION
Cooling Mode
- Thermostat energizes "O" whenever the mode is "Cool'
- Thermostat energizes "Y' and "G" when there is a demand for cooling.
Heating Mode
- Above 40 Deg (adjustable Setup# 312)
- The thermostat will energize "Y" and "G" when there is a demand for heating.
- If the space temperature drops more than 2 deg (adjustable Setup# 309) the thermostat will disable the compressor output "Y" and energize the backup heat output "W".
- Whenever the Backup Heat source energizes it will stay on until the call for heat satisfies (adjustable Setup# 302).
- Below 40 Deg (adjustable Setup# 312)
- The thermostat will energize "W" when there is a demand for heating.
Em Heat Mode
- The thermostat will energize "W" when there is a demand for heating.