Honeywell Thermostats: TH8320R & TH8321R
Re: Configure the thermostat for a 1-Stage Add-On Heat Pump
Step 1: Go to "Installer Setup"
Step 2: Enter Setup Information below:
Setup# | Description | Option |
101 | APPLICATION | "residential" or "commercial" |
103 | THERMOSTAT NAME | Select Appropriate Name |
104 | THERMOSTAT TYPE | "programmable" (optional) |
105 | TEMPERATURE SCALE | "farenheit" |
106 | OUTDOOR AIR SENSOR | "Yes" |
200 | HEATING SYSTEM | "heat pump" |
201 | HEATING EQUIPMENT | "air to air heat pump" |
206 | REVERSING VALVE | "o (o/b on cool)" |
207 | COMPRESSOR STAGES | 1 |
207 | BACKUP HEAT STAGES | 1 |
218 | BACKUP HEAT TYPE | "Gas/Oil" |
219 | EXTERNAL FOSSIL FUEL KIT | "No" |
300 | SYSTEM CHANGEOVER | "automatic" |
300 | AUTO CHANGE DEADBAND | 3 |
301 | CONTROL OPTIONS | "advanced options" |
302 | FINISH WITH HIGH HEAT | "Yes" |
309 | BACKUP HEAT DROOP | 2.0 |
311 | UPSTAGE TIMER BACKUP HT | Off |
312 | OUTDOOR LOCKOUT H/P | 40 Deg |
312 (a) | O/D LOCKOUT BACKUP HEAT | Off |
314 | COMPRESSOR CYCLES STG 1 | 3 |
316 | BACKUP HEAT CYCLES PER HR | 5 |
324 | COMPRESSOR OFF TIME | 3 minutes |
326 | EXTENDED FAN RUN IN COOL | Off |
326 | EXTENDED FAN RUN IN HEAT | Off |
400 | SCHEDULE PERIODS | "4 periods per day" |
401 | PRE-OCCUPANCY PURGE | Off |
402 | TYPE OF OVERRIDE | standard |
403 | OVERRIDE DURRATION | 4 hours |
405 | MIN HEAT RECOVERY RATE | 3º/hr |
407 | MIN COOL RECOVERY RATE | 5º/hr |
409 | ADAPTIVE RECOVERY | Yes |
410 | MINIMUM COOL SETPOINT | 64 deg |
410 | MAXIMUM HEAT SETPOINT | 82 deg |
411 | KEYPAD LOCKOUT | "Unlocked" |
500 | WIRED SENSOR ON S TERMINAL | Yes |
500 (a) | WIRED INDOOR SENSOR | No |
500 (b) | WIRED OUTDOOR SENSOR | Yes |
500 (c) | WIRED DISCHARGE AIR SENSOR | No |
505 | O/D SENSOR TERMINAL S1 | <Next> |
700 | FILTER TYPE | "media" |
702 | NUMBER OF AIR FILTERS | 1 |
711 | AIR FILTER | "reminder-off" |
800 | HUMIDIFIER TYPE | "none" or "bypass-fan/pwrd" |
803 | HUMIDIFIER WIRING | "t-stat terminal U1" |
805 | WINDOW PROTECTION | Off |
806 | USE HIMIDIFIER IN HEAT MODE | Yes |
806 | USE HUMIDIFIER IN OFF MODE | No |
807 | HUMIDIFIER CONTROL | "hum when heat is on" |
810 | HUMIDIFIER PAD | "reminder-off" |
900 | DEHUM EQUIPMENT | "A/C with high fan" |
907 | DEHUM OVER COOLING LIMIT | 1 deg |
918 | DEHUM AWAY MODE | "not allowed" |
921 | DEHUMIDIFIER FILTER | "reminder-off" |
1000 | VENTILATION TYPE | "none" |
1017 | VENTILATION FILTER | "reminder-off" |
1100 | NUMBER OF UV DEVICES | 0 |
1200 | CUSTOM REMINDERS | |
28 | BACKLIGHTING | "continuous" |
1400 | CLOCK FORMAT | "12 hour" |
1401 | DAYLIGHT SAVING TIME | On |
1402 | INDOOR TEMPERATURE OFFSET | 0 deg |
1402 | SHOW HUMIDITY | Yes |
1402 | INDOOR HUMIDITY OFFSET | 0% |
1404 | ALERT LIGHT INDICATOR | On |
1500 | DEALER NAME | "GHAC, INC" |
1500 | DEALER PHONE | 606-836-8143 |
1501 | DEALER EMAIL | service@ghacinc.com |
1501 | DEALER WEBSITE | www.ghacinc.com |
1502 | DEALER MESSAGE |
Step 3: Press "Done"
Step 4: Press "HOME" to go back to the Home Screen.
WIRING
Thermostat | Furnace | Heat Pump |
R | R | R |
C | C | C |
G | G | |
W/Aux | W | W, W1, or X (Trane) |
Y | Y or Y/Y2 | Y |
O | (wire nut) | O |
S1* | (wire nut) | O/D Sensor 1 |
S1* | (wire nut) | O/D Sensor 2 |
* If using a wired outdoor air sensor.
SEQUENCE OF OPERATION
Cooling Mode
Heating Mode
Em Heat Mode