Configure TH8320U for Add-On Heat Pump

Article ID: 51
Last updated: 6 Feb, 2023

Honeywell Thermostat: TH8320U

Re: ADD-ON HEAT PUMP

The TH8320U VisionPro thermostat is capable of direct-control of an add-on heat pump system. (Does not apply to York units with Yorkguard Module)

Requirements:

  • TH8320U Thermostat
  • C7089U Outdoor Sensor
  • Minimum #8 (preferably #10) stat wire between Heat Pump & Furnace
  • Minimum #8 (preferably #10) stat wire between Furnace & Thermostat

CONFIGURE THERMOSTAT:

  • Enter "Installer Setup".
  • Modify the items in the chart below.
  • Press "Done" to exit "Installer Setup" and save changes.
Setup# Description Value Description
170 System Type 7 2Ht/1Cl Heat Pump
190 Reversing Valve 0 Cooling Changeover
200 Backup Heat 1 Gas
210 Fossil Fuel Control 0 Thermostat-Controlled
340 Remote Sensor 2 Outdoor for Control
350 Compressor Lockout 40 40 Degrees

WIRING:

Thermostat Furnace Heat Pump
R R R
C C C
G G
W/Aux W W or W1 or 66 or X (Trane)
Y Y or Y/Y2 Y
O (wire nut) O
S1 (wire nut) O/D Sensor 1
S1 (wire nut) O/D Sensor 2

SEQUENCE OF OPERATION:

Cooling Mode 

  • Thermostat energizes "O" whenever the mode is "Cool'
  • Thermostat energizes "Y' and "G" when there is a demand for cooling.

Heating Mode

  • When the outdoor temperature is above 40 deg (adjustable Setup# 350) the thermostat will energize "Y" and "G" when there is a demand for heating.
  • When the outdoor temperature is below 40 deg (adjustable Setup# 350) the thermostat will energize "W" when there is a demand for heating.

Em Heat Mode

  • The thermostat will energize "W" when there is a demand for heating.