Knowledgebase

TH8320U - 2Ht/1Cl Conventional Setup

Article ID: 465
Last updated: 6 Feb, 2023

Honeywell Thermostat: TH8320U

Re: 2HT/1CL Conventional Setup

To enter Installer Setup:

  • Touch the "System" button.
    • The center squares at the bottom of the screen should display empty.
  • Touch and Hold the empty squares to the Right & Left of the Center square.

Setup# Description Values
120 First 2 digits of Year
  • 20
130 Last 2 digits of Year
140 Calendar Month
  • 01 - 12
150 Day of the Month
  • 01 - 31
160

Schedule Options

  • 0=Non-Prog
  • 4=Programmable
170 System Type
  • 9=2Ht/1Cl Conventional
180

Fan Operation

  • 0=Gas
220 Compressor 1 CPH
  • 3
240

Heat 1 Cycles/Hr

  • 3=90% Furnace
250 Heat 2 Cycles/Hr
  • 3=90% Furnace
280 Backlight
  • 1=Continuous
290

Additional Choices

  • 1=All Choices
300

Changeover Type

  • 1=Automatic
310 Changeover Deadband
  • 3
320 Temperature Scale
  • 0=Farenheit
330 Daylight Savings
  • 2=New Dates
340 Remote Temperature
  • 0=None
500 Filter Reminder
  • 0=Off
510

Humidifier Reminder

  • 0=Off
520

UV Reminder

  • 0=Off,
530 Intelligent Recovery
  • 1=On
540

Programmable Periods

  • 4
580 Compressor Delay
  • 5
600 Highest Heat Temp
  • 82
610 Lowest Cool Temp
  • 65
640 Clock Format
  • 12=12 Hour
650 Extend Fan Time (Heat)
  • 0
660

Extend Fan Time (Cool)

  • 0
670 Keypad Lockout
  • 0=Unlocked
680 Temperature Control (Heat)
  • 2=Standard
690 Temperature Control (Cool)
  • 2=Standard
700 Temperature Display Offset
  • 0
710 Thermostat Reset
  • 0=No reset

This article was:   Helpful | Not helpful
Report an issue
Article ID: 465
Last updated: 6 Feb, 2023
Revision: 6
Access: Public
Views: 58