Honeywell Thermostat: TH6220U T6 Pro

Re: 2Ht/2Cl Conventional Setup

To enter Installer Setup:

  • Press and hold the "Center" button and the "+" button together for 3 seconds.
  • Press "Select" to enter Setup.
  • Press "Select" to cycle through setup options.
  • Press "+" or "-" to change values.
  • Press "Select" to confirm changes or "Back" to ignore changes.
  • To Finish and Save changes, press "Home".

Setup# Function Options
120 Schedule Options
  • 0 = Non-Programmable
  • 2 = 5/2 Programmable
  • 3 = 5/1/1 Programmable
  • 4 = 7 Day Programmable
125 Temperature Scale
  • 0 = Farenheit
130

Outdoor Sensor

  • 0 = None
200

Heat Equipment

  • 1 = Conventional
205 Heat Type
  • 1 = Standard Eff Gas
220 Cool Stages
  • 2
221 Heat Stages
300 System Changeover
  • 1 = Automatic
303 Auto Changeover Differential
  • 2 Deg F.
365 Cool 1 Cycle Rate
  • 3
366 Cool 2 Cycle Rate
  • 3
370 Heat 1 Cycle Rate
  • 5
371 Heat 2 Cycle Rate
  • 5
387 Short-Cycle Time
  • 3
425 Intelligent Recovery
  • 1 = Yes
430 Min Cool Setpt
  • 64 Deg F.
431 Max Heat Setpt
  • 82 Deg F.
435 Keypad Lockout
  • 0 = None
  • 1 = Partial
  • 2 = Full
500 Wired Indoor Sensor
  • 0 = No
702 Air Filter Qty
  • 1
711 Filter 1 Timer
  • 0 = Off
1400 Backlight
  • 1 = Continuous
1401 Brightness
  • 3
1410 Clock
  • 12
1415 Daylight Savings
  • 1 = On
1420 Temperature Offset
  • 0 Deg F.