Honeywell Thermostat: TH6220U T6 Pro
Re: Installer Setup Options
To enter Installer Setup:
- Press and hold the "Center" button and the "+" button together for 3 seconds.
- Press "Select" to enter Setup.
- Press "Select" to cycle through setup options.
- Press "+" or "-" to change values.
- Press "Select" to confirm changes or "Back" to ignore changes.
- To Finish and Save changes, press "Home".
Setup# |
Function |
Options |
120 |
Schedule Options |
- 0 = Non-Programmable
- 2 = 5/2 Programmable
- 3 = 5/1/1 Programmable
- 4 = 7 Day Programmable
|
125 |
Temperature Scale |
- 0 = Farenheit
- 1 = Celsius
|
130 |
Outdoor Sensor
|
- 0 = None
- 1 = Wired Outdoor Sensor
|
200 |
Heat Equipment
|
- 1 = Conventional
- 2 = Heat Pump
- 3 = Radiant Heat
- 5 = None (Cool Only)
|
205 |
Heat Type |
- 1 = Standard Eff Gas
- 2 = High Eff Gas
- 3 = Oil Furnace
- 4 = Electric Furnace
- 7 = Air to Air Heat Pump
- 8 = Geothermal Heat Pump
- 9 = Hot Water Radiant
- 12 = Steam
|
218 |
Reversing Valve |
- 0 = O/B Energizes in Cool
- 1 = O/B Energizes in Heat
|
220 |
Cool Stages |
|
221 |
Heat/Backup Stages |
- Heat Stages = 1 or 2
- Backup Stages = 0 or 1
|
230 |
Heat Fan Control |
- 1 = Equipment Controls Fan
- 2 = Thermostat Controls Fan
|
255 |
Backup Heat |
- 1 = Electric Furnace
- 2 = Gas Furnace
|
260 |
Fossil Fuel Control |
- 0 = Thermostat Controls
- 1 = External Fossil Fuel Kit
|
270 |
Backup Heat Fan
|
- 1 = Equipment Controls Fan
- 2 = Thermostat Controls Fan
|
271 |
Em Heat Fan |
- 50 = Lowest cooling temperature setting
- 51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
|
300 |
System Changeover |
|
303 |
Auto Changeover Differential |
|
340 |
Backup Heat Droop |
- 0 = Comfort
- 2 to 15 Deg F.
|
350 |
Backup Ht Upstage Timer |
- 0 = Off
- 1 = 30 Min
- 2 = 45 Min
- 3 = 60 Min
- 4 = 75 Min
- 5 = 90 Min
- 6 = 2 Hrs
- 7 = 3 Hrs
- 8 = 4 Hrs
- 10 = 5 Hrs
|
355 |
Compressor Lockout |
- -- = Off
- 5 to 60 Deg F (5 Deg Increments)
|
356 |
Aux Heat Lockout |
- -- = Off
- 5 to 65 Deg F (5 Deg Increments)
|
365 |
Cool 1 Cycle Rate |
|
366 |
Cool 2 Cycle Rate |
|
370 |
Heat 1 Cycle Rate |
|
371 |
Heat 2 Cycle Rate |
|
375 |
Aux Ht Cycle Rate |
|
387 |
Short-Cycle Time |
|
425 |
Intelligent Recovery |
|
430 |
Min Cool Setpt |
|
431 |
Max Heat Setpt |
|
435 |
Keypad Lockout |
- 0 = None
- 1 = Partial
- 2 = Full
|
500 |
Wired Indoor Sensor |
|
515 |
Sensor Type |
|
520 |
Sensor Control |
- 1 = Thermostat
- 2 = Wired
- 3 = Average
|
702 |
Air Filter Qty |
|
711 |
Filter 1 Timer |
- 0 = Off
- 1 = 10 Run Days
- 2 = 20 Run Days
- 3 = 30 Run Days
- 4 = 45 Run Days
- 5 = 60 Run Days
- 6 = 90 Run Days
- 7 = 120 Run Days
- 8 = 150 Run Days
- 9 = 30 Calendar Days
- 10 = 45 Calendar Days
- 11 = 60 Calendar Days
- 12 = 75 Calendar Days
- 13 = 3 Calendar Months
- 14 = 4 Calendar Months
- 15 = 5 Calendar Months
- 16 = 6 Calendar Months
- 17 = 9 Calendar Months
- 18 = 12 Calendar Months
- 19 = 15 Calendar Months
|
712 |
Filter 2 Timer |
- 0 = Off
- 1 = 10 Run Days
- 2 = 20 Run Days
- 3 = 30 Run Days
- 4 = 45 Run Days
- 5 = 60 Run Days
- 6 = 90 Run Days
- 7 = 120 Run Days
- 8 = 150 Run Days
- 9 = 30 Calendar Days
- 10 = 45 Calendar Days
- 11 = 60 Calendar Days
- 12 = 75 Calendar Days
- 13 = 3 Calendar Months
- 14 = 4 Calendar Months
- 15 = 5 Calendar Months
- 16 = 6 Calendar Months
- 17 = 9 Calendar Months
- 18 = 12 Calendar Months
- 19 = 15 Calendar Months
|
1400 |
Backlight |
- 0 = On Demand
- 1 = Continuous
|
1401 |
Brightness |
|
1410 |
Clock |
|
1415 |
Daylight Savings |
|
1420 |
Temperature Offset |
|