TH5220 - Setup Options

Article ID: 222
Last updated: 6 Feb, 2023

Honeywell Thermostat: TH5220D FocusPro

Re: Installer Setup Options

To enter Installer Setup, press and hold the "Fan" button and the "Up" button together until the display changes.

Setup# Function Options
1 System Type
  • 0 = Gas, oil or electric heat with air conditioning
  • 1 = 1 heat/1 cool heat pump
  • 2 = Heat only (2-wire systems/power to open & close zone valves/normally open zone valves)
  • 3 = Heat only with fan
  • 4 = Cool only
  • 5 = 2 heat/1 cool heat pump
  • 6 = 2 heat/2 cool conventional
  • 7 = 2 heat/1 cool conventional
  • 8 = 1 heat/2 cool conventional
2 Rev Valve
  • 0 = Changeover valve (O/B terminal energized in cooling)
  • 1 = Changeover valve (O/B terminal energized in heating)
3

Fan Control

  • 0 = Gas or oil furnace — equipment controls fan in heating
  • 1 = Electric furnace — thermostat controls fan inheating
5

Heat Cycle Rate

  • 5 = For gas or oil furnaces of less than 90%efficiency
  • 1 = For steam or gravity systems
  • 3 = For hot water systems & furnaces of over 90% efficiency
  • 9 = For electric furnaces
  • [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
6 2nd Stg Ht Cycle Rate
  • 5 = For gas or oil furnaces of less than 90%efficiency
  • 1 = For steam or gravity systems
  • 3 = For hot water systems & furnaces of over 90% efficiency
  • 9 = For electric furnaces
  • [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
8 Em Ht Cycle Rate
  • 5 = For gas or oil furnaces of less than 90%efficiency
  • 1 = For steam or gravity systems
  • 3 = For hot water systems & furnaces of over 90% efficiency
  • 9 = For electric furnaces
  • [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
9 Compressor Cycle Rate
  • 3 = Recommended for most compressors
  • [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10 2nd Stg Cycle Rate
  • 3 = Recommended for most compressors
  • [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
12 Changeover Type
  • 0 = Manual changeover (Heat/Cool/Off)
  • 1 = Auto changeover (Heat/Cool/Auto/Off)
  • 2 = Auto changeover only (Auto)
14 Temperature Display
  • 0 = Fahrenheit
  • 1 = Celsius
15 Compressor Off Delay
  • 5 = Five-minute compressor off time
  • [Other options: 0, 1, 2, 3 or 4-minute off time]
27

Heat Stop

  • 90 = Highest heating temperature setting
  • 40-89 Heating temperature range (increments of 1°F, or 0.5°C)
28

Cool Stop

  • 50 = Lowest cooling temperature setting
  • 51-99 Cooling temperature range (increments of 1°F, or 0.5°C)