Honeywell Thermostat: TH5220D FocusPro
Re: Installer Setup Options
To enter Installer Setup, press and hold the "Fan" button and the "Up" button together until the display changes.
Setup# |
Function |
Options |
1 |
System Type |
- 0 = Gas, oil or electric heat with air conditioning
- 1 = 1 heat/1 cool heat pump
- 2 = Heat only (2-wire systems/power to open & close zone valves/normally open zone valves)
- 3 = Heat only with fan
- 4 = Cool only
- 5 = 2 heat/1 cool heat pump
- 6 = 2 heat/2 cool conventional
- 7 = 2 heat/1 cool conventional
- 8 = 1 heat/2 cool conventional
|
2 |
Rev Valve |
- 0 = Changeover valve (O/B terminal energized in cooling)
- 1 = Changeover valve (O/B terminal energized in heating)
|
3 |
Fan Control
|
- 0 = Gas or oil furnace — equipment controls fan in heating
- 1 = Electric furnace — thermostat controls fan inheating
|
5 |
Heat Cycle Rate
|
- 5 = For gas or oil furnaces of less than 90%efficiency
- 1 = For steam or gravity systems
- 3 = For hot water systems & furnaces of over 90% efficiency
- 9 = For electric furnaces
- [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
|
6 |
2nd Stg Ht Cycle Rate |
- 5 = For gas or oil furnaces of less than 90%efficiency
- 1 = For steam or gravity systems
- 3 = For hot water systems & furnaces of over 90% efficiency
- 9 = For electric furnaces
- [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
|
8 |
Em Ht Cycle Rate |
- 5 = For gas or oil furnaces of less than 90%efficiency
- 1 = For steam or gravity systems
- 3 = For hot water systems & furnaces of over 90% efficiency
- 9 = For electric furnaces
- [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
|
9 |
Compressor Cycle Rate |
- 3 = Recommended for most compressors
- [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
|
10 |
2nd Stg Cycle Rate |
- 3 = Recommended for most compressors
- [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
|
12 |
Changeover Type |
- 0 = Manual changeover (Heat/Cool/Off)
- 1 = Auto changeover (Heat/Cool/Auto/Off)
- 2 = Auto changeover only (Auto)
|
14 |
Temperature Display |
- 0 = Fahrenheit
- 1 = Celsius
|
15 |
Compressor Off Delay |
- 5 = Five-minute compressor off time
- [Other options: 0, 1, 2, 3 or 4-minute off time]
|
27 |
Heat Stop
|
- 90 = Highest heating temperature setting
- 40-89 Heating temperature range (increments of 1°F, or 0.5°C)
|
28 |
Cool Stop
|
- 50 = Lowest cooling temperature setting
- 51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
|