1050
|
Temperature Indication Scale
|
- F = Fahrenheit
- C = Celsius
|
|
1060
|
Outdoor Sensor (TH1210U4001 & TH1320U4002 only. For lockouts only. Does not display)
|
- 0 = None
- 1 = Wired Outdoor Sensor
|
|
2000
|
Heating System Type (default setting varies by model)
|
- 1 = Conventional Forced Air Heat
- 2 = Heat Pump
- 3 = Radiant Heat
- 5 = None (Cool Only)
|
|
2010
|
Heating Equipment Type
|
Conventional Forced Air Heat:
- 1 = Standard Efficiency Gas Forced Air
- 2 = High Efficiency Gas Forced Air
- 3 = Oil Forced Air
- 4 = Electric Forced Air
- 5 = Hot Water Fan Coil
Heat Pump:
- 7 = Air to Air Heat Pump
- 8 = Geothermal Heat Pump
Radiant Heat:
- 9 = Hot Water Radiant Heat
- 12 = Steam
|
|
2060
|
Reversing Valve O/B
|
- 0 = O (O/B in Cool)
- 1 = B (O/B in Heat)
|
|
2070
|
Compressor Stages
|
- 0, 1, 2
- Note: Only 1 compressor stage available on TH1110U4000 & TH1210U4001
|
|
2071
|
Heat Stages / Backup Heat Stages
|
- Heat Stages: 1, 2
- Backup Heat Stages: 0, 1 (TH1210U4001 & TH1320U4002 only)
|
|
2110
|
Fan Control in Heat
|
- 1 = Equipment Controls Fan
- 2 = Thermostat Controls Fan
- Note: Only shown if 2010 = 4 or 5
|
|
2175
|
Aux/E terminal control
(TH1210U4001 & TH1320U4002 only)
|
- 0 = Drive both Aux & E together
- 1 = Aux and E independent
|
|
2180
|
Backup Heat Source (Heat Pump Only)
(TH1210U4001 & TH1320U4002 only)
|
- 31 = Electric Forced Air
- 32 = Standard Efficiency Gas Forced Air
- 33 = High Efficiency Gas Forced Air
- 34 = Oil Forced Air, Hot Water Fan Coil
- 36 = Hot Water Radiant Heat
|
|
2185
|
Emergency Heat Source
(TH1210U4001 & TH1320U4002 only)
|
|
3000
|
System Changeover
|
|
|
3015
|
Auto Changeover Differential
|
- 0 °F to 5 °F
- 0.0 °C to 2.5 °C
Note: The Differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (Heat or Cool) to the opposite mode when the thermostat is in auto-changeover.
|
|
3020
|
Finish With High Cool Stage
|
Note: TH1320U4002 only.
|
|
3021
|
Finish With High Heat Stage
|
Note: TH1210U4001 & TH1320U4002 only.
|
|
3090
|
Backup Heat Droop
|
- [0] = Comfort
- 2 °F to 15 °F (in 1 °F increments)
- 1.0 °C to 7.5 °C (in 0.5 °C increment).
Note: 0 (comfort) setting only available if Backup Heat (ISU 2180) is set to Electric. (TH1210U4001 & TH1320U4002 only.)
|
|
3110
|
Upstage Timer for Backup Heat
|
- 0 = Off
- 1 = 30 minutes
- 2 = 45 minutes
- 3 = 60 minutes
- 4 = 75 minutes
- 5 = 90 minutes
- 6 = 2 hours
- 7 = 3 hours
- 8 = 4 hours
- 9 = 5 hours
- 10 = 6 hours
- 11 = 8 hours
- 12 = 10 hours
- 13 = 12 hours
- 14 = 14 hours
- 15 = 16 hours
Note: (TH1210U4001 & TH1320U4002 only) If 3090 = 0 and 2180 = 31, 3110 only has settings 0-3).
|
|
3120
|
Compressor Lockout / Balance Point (TH1210U4001 & TH1320U4002 only)
|
- 0 = Off
- 1 = -15°F (-26°C)
- 2 = -10°F (-23.5°C)
- 3 = -5°F (-20.5°C)
- 4 = 0°F (-18°C)
- 5 = 5°F (-15°C)
- 10 = 10°F (-12°C)
- 15 = 15°F (-9.5°C)
- 20 = 20°F (-6.5°C)
- 25 = 25°F (-4°C)
- 30 = 30°F (-1°C)
- 35 = 35°F (1.5°C)
- 40 = 40°F (4.5°C)
- 45 = 45°F (7°C)
- 50 = 50°F (10°C)
- 55 = 55°F (13°C)
- 60 = 60°F (15.5°C)
|
|
3121
|
Outdoor Lockout Backup Heat
(TH1210U4001 & TH1320U4002 only)
|
- 0 = Off
- 5 = 5°F (-15°C)
- 10 = 10°F (-12°C)
- 15 = 15°F (-9.5°C)
- 20 = 20°F (-6.5°C)
- 25 = 25°F (-4°C)
- 30 = 30°F (-1°C)
- 35 = 35°F (1.5°C)
- 40 = 40°F (4.5°C)
- 45 = 45°F (7°C)
- 50 = 50°F (10°C)
- 55 = 55°F (13°C)
- 60 = 60°F (15.5°C)
- 65 = 65°F (18.5°C)
|
|
3125
|
Lockout Fan after a Cool call
|
- [0] = Off
- 1 = 5 min
- 2 = 10 min
- 3 = 15 min
- 4 = 20 min
- 5 = 25 min
- 6 = 30 min
- 7 = 35 min
- 8 = 40 min
- 9 = 45 min
- 10 = 50 min
- 11 = 55 min
- 12 = 60 min
- 13 = 65 min
- 14 = 70 min
- 15 = 75 min
- 16 = 80 min
- 17 = 85 min
- 18 = 90 min
- 19 = 95
- 20 = 100 min
- 21 = 105 min
- 22 = 110 min
- 23 = 115 min
- 24 = 120 min
|
|
3140
|
Compressor Cycle Rate (Stage 1)
|
|
|
3141
|
Compressor Cycle Rate (Stage 2)
|
|
|
3150
|
Heating Cycle Rate (Stage 1)
|
|
|
3151
|
Heating Cycle Rate (Stage 2)
|
- 1 - 12 (TH1320U4002 only)
|
|
3160
|
Heating Cycle Rate Auxiliary Heat
|
- 1 - 12 (TH1210U4001 & TH1320U4002 only)
|
|
3165
|
Heating Cycle Rate Emergency Heat
|
- 1 - 12 (TH1210U4001 & TH1320U4002 only)
|
|
3240
|
Compressor Protection
|
|
|
4100
|
Maximum Cool Setpoint
|
- 50°F to 99°F
- 10.0°C to 37.0°C
|
|
4101
|
Minimum Cool Setpoint
|
- 50°F to 99 °F
- 10.0°C to 37.0 °C
|
|
4102
|
Maximum Heat Setpoint
|
- 40°F to 90°F
- 4.5°C to 32.0°C
|
|
4103
|
Minimum Heat Setpoint
|
- 32 °F to 50 °F (Default is 40 °F)
- 0 °C to 10.0 °C (Default is 4.5 °C)
|
|
7110
|
Air Filter Replacement Reminder
|
- 0 = Off
- 1 = 10 Run Time Days
- 2 = 20 Run Time Days
- 3 = 30 Run Time Days
- 4 = 45 Run Time Days
- 5 = 60 Run Time Days
- 6 = 90 Run Time Days
- 7 = 120 Run Time Days
- 8 = 150 Run Time Days
- 9 = 30 Calendar Days
- 10 = 45 Calendar Days
- 11 = 60 Calendar Days
- 12 = 75 Calendar Days
- 13 = 3 Calendar Months
- 14 = 4 Calendar Months
- 15 = 5 Calendar Months
- 16 = 6 Calendar Months
- 17 = 9 Calendar Months
- 18 = 12 Calendar Months
- 19 = 15 Calendar Months
|
|
14003
|
Backlighting
|
- 0 = On Demand
- 1 = Continuous
Note: Common wire needed for continuous.
|
|
14004
|
Backlight brightness
|
Note: Only displayed if Continuous backlight selected.
|
|
14005
|
Idle screen selection
|
- 0 - Minimum Information shown
- 2 - Maximum display information shown
|
|
14020
|
Temperature Display Offset
|
- -3°F to 3°F (0)
- -1.5°C to 1.5°C (0)
|