TH5220 - Configure 2Ht/1Cl Heat Pump

Article ID: 74
Last updated: 30 Mar, 2018

Honeywell Thermostat: TH5220D / TH6220D FOCUSPRO

Re: Configure for 2Ht/1Cl Heat Pump


Step 1: Go to "Installer Setup"

  • Press and hold the "UP" button and the "FAN" button until the setup screen appears.

Step 2: Enter the Setup Information below:

  • Use the "UP" and "DOWN" buttons to change settings.
  • Use the "NEXT" button to advance to the new Setup#.
Setup# Description Option
1 System Type 5 = 2 heat/1 cool heat pump
2 Reversing Valve 0 = O/B energized in cooling
6 2nd Stg Heat Cycle Rate 9 = Electric heat
8 Em Ht Cycle Rate 9 = Electric heat
9 Compressor Cycle Rate 3
12 Changeover Type 1 = Automatic
14 Temperature Display 0 = Fahrenheit
15 Compressor Off Delay 3 = 3 Minutes
27 Heat Stop 82 deg
28 Cool Stop 64 deg

Step 3: Press the "Done" button to save changes. 