Honeywell Thermostats: TH8320R & TH8321R
Re: Configure the thermostat for 2 Heat / 1 Cool
Step 1: Go to "Installer Setup"
- From the HOME Screen press the MENU tab
- Scroll down and select "Installer Options"
- Enter Factory Password
- Select "Installer Setup"
Step 2: Enter Setup Information below:
Setup# |
Description |
Option |
101 |
APPLICATION |
"residential" or "commercial" |
103 |
THERMOSTAT NAME |
Select Appropriate Name |
104 |
THERMOSTAT TYPE |
"programmable" |
105 |
TEMPERATURE SCALE |
"farenheit" |
106 |
OUTDOOR AIR SENSOR |
Optional |
200 |
HEATING SYSTEM |
"conv. forced air" |
207 |
COOL STAGES |
1 |
207 |
HEAT STAGES |
2 |
211 |
FAN CONTROL IN HEAT |
"equip controls fan" |
222 |
A-L/A TERMINAL |
"none" |
300 |
SYSTEM CHANGEOVER |
"automatic" |
300 |
AUTO CHANGE DEADBAND |
3 |
301 |
CONTROL OPTIONS |
"advanced options" |
302 |
FINISH WITH HIGH COOL |
No |
302 |
FINISH WITH HIGH HEAT |
No |
306 |
HEAT DIFFERENTIAL STAGE 2 |
"comfort' |
314 |
COOL CYCLES PER HR STAGE 1 |
3 |
315 |
HEAT CYCLES PER HR STAGE 1 |
6 |
315 |
HEAT CYCLES PER HR STAGE 2 |
6 |
324 |
COMPRESSOR OFF TIME |
3 minutes |
326 |
EXTENDED FAN RUN IN COOL |
Off |
326 |
EXTENDED FAN RUN IN HEAT |
Off |
400 |
SCHEDULE PERIODS |
"4 periods per day" |
401* |
PRE-OCCUPANCY PURGE |
Off |
402* |
TYPE OF OVERRIDE |
standard |
403* |
OVERRIDE DURATION |
4 hours |
405* |
MIN HEAT RECOVERY RATE |
5º/hr |
407* |
MIN COOL RECOVERY RATE |
3º/hr |
409 |
ADAPTIVE RECOVERY |
Yes |
410 |
MINIMUM COOL SETPOINT |
64 deg |
410 |
MAXIMUM HEAT SETPOINT |
82 deg |
411 |
KEYPAD LOCKOUT |
"Unlocked" |
500 |
WIRED SENSOR ON S TERMINAL |
No |
700 |
FILTER TYPE |
"media" |
702 |
NUMBER OF AIR FILTERS |
1 |
711 |
AIR FILTER |
"reminder-off" |
800* |
HUMIDIFIER TYPE |
"none" or "bypass-fan/pwrd" |
803* |
HUMIDIFIER WIRING |
"t-stat terminal U1" |
805* |
WINDOW PROTECTION |
Off |
806* |
USE HIMIDIFIER IN HEAT MODE |
Yes |
806* |
USE HUMIDIFIER IN OFF MODE |
No |
807* |
HUMIDIFIER CONTROL |
"hum when heat is on" |
810 |
HUMIDIFIER PAD |
"reminder-off" |
900* |
DEHUM EQUIPMENT |
"A/C with high fan" |
907* |
DEHUM OVER COOLING LIMIT |
1 deg |
918* |
DEHUM AWAY MODE |
"not allowed" |
921* |
DEHUMIDIFIER FILTER |
"reminder-off" |
1000 |
VENTILATION TYPE |
"none" |
1017 |
VENTILATION FILTER |
"reminder-off" |
1100 |
NUMBER OF UV DEVICES |
0 |
1105 |
UV BULB |
"reminder-off" |
1200 |
CUSTOM REMINDERS |
|
28 |
BACKLIGHTING |
"continuous" |
1400 |
CLOCK FORMAT |
"12 hour" |
1401 |
DAYLIGHT SAVING TIME |
On |
1402 |
INDOOR TEMPERATURE OFFSET |
0 deg |
1404 |
ALERT LIGHT INDICATOR |
On |
1500 |
DEALER NAME |
"GHAC, INC" |
1500 |
DEALER PHONE |
606-836-8143 |
1501 |
DEALER EMAIL |
service@ghacinc.com |
1501 |
DEALER WEBSITE |
www.ghacinc.com |
1502 |
DEALER MESSAGE |
|
- TH8321R Options Only
- Commercial Options Only
Step 3: Press "Done"
- "Do you want to exit Installer Setup? Press "Yes"
- "Do you want to save changes?" Press "Yes"
Step 4: Press "HOME" to go back to the Home Screen.