TH5320R - Configure 2 Heat / 1 Cool Heat Pump

Article ID: 675
Last updated: 6 Feb, 2023

Honeywell Thermostat: TH5320R Wireless FocusPro

Re: Configure 2 Heat / 1 Cool Heat Pump

To enter Installer Setup, press and hold the "Fan" button and the "Up" button together until the display changes.

Setup# Function Options
0 Zone Number
  • 0 = Leave at "0"
1 System Type
  • 5 = 2 heat/1 cool heat pump
2 Rev Valve
  • 0 = Changeover valve (O/B terminal energized in cooling)
4

Backup Heat

  • 1 = Electric
6 2nd Stg Ht Cycle Rate
  • 9 = For electric furnaces
8 Em Ht Cycle Rate
  • 9 = For electric furnaces
9 Compressor Cycle Rate
  • 3 = Recommended for most compressors
11 Heat Pump Type
  • 0 = Air-to-Air Heat Pump
12 Changeover Type
  • 1 = Auto changeover (Heat/Cool/Auto/Off)
14 Temperature Display
  • 0 = Fahrenheit
15 Compressor Off Delay
  • 3 = Three-minute compressor off time
22 Outdoor Air Sensor
  • 0 = No
26 Aux Heat Control
  • 1 = Economy
27

Heat Stop

  • 82 = Highest heating temperature setting
28

Cool Stop

  • 64 = Lowest cooling temperature setting
32

Indoor Temp Display Offset

  • 0 = No offset
33

Outdoor Temp Display Offset

  • 0 = No offset
35

Humidity Display Offset

  • 3 = No Offset
36

Thermostat Name

  • 52 = Thermostat
39

Wireless Setup

  • 0 = Disconnect thermostat from wireless system
  • 1 = Thermostat is connected
90

Reset

  • 0 = No reset
  • 1 = Reset thermostat back to factory configuration