Knowledgebase

T8524D / T8624D Installer Setup

Article ID: 348
Last updated: 5 Oct, 2017

Honeywell Thermostat: T8524D / T8624D

Re: Installer Setup Options

The Installer Setup is used to customize the thermostat to specific systems.

A combination of key presses are required to use the Installer Setup feature.

To enter the Installer Setup - press and hold the Information [i] key with the increase ▲ and decrease ▼ keys until the first number is displayed.

  • To advance to the next Installer Setup, press the Information [i] key.
  • To change a setting, use the increase ▲ and decrease ▼ keys.
  •  To exit the Installer Setup, press and hold the Information [i] key until the display returns to normal (approximately three seconds).

  • T8524D & T8624D
  • T8624D Only
Setup# Function Options
1 Not Used Not Used
2 Heating Fan
  • 0 = Equipment controls
  • 1 = T-stat controls
3 Not Used Not Used
4

Heat Cycle Rate 1

  • 3-9
5 2nd Stg Ht Cycle Rate
  • 3-9
6 Not Used Not Used
7 Not Used Not Used
8 Not Used Not Used
9 Not Used Not Used
10 Not Used Not Used
11 Not Used Not Used
12 Changeover
  • 0 = Auto Changeover
  • 1 = Manual
  • 2 = Fixed Auto
13 Adaptive Recovery
  • 0 = On
  • 1 = Off
14 Temperature Display
  • 0 = Fahrenheit
  • 1 = Celsius
15 Not Used Not Used
16 Clock
  • 0=12 Hour
  • 1 = 24 Hour
17 Not Used Not Used
18 Not Used Not Used
19 Extended Fan - Heat
  • 0 = No extended fan
  • 1 = 90 sec. extended
20 Extended Fan - Cool
  • 0 = No extended fan
  • 1 = 90 sec. extended
21 Not Used Not Used
22 Not Used Not Used
23 Not Used Not Used
24 Outdoor Temp
  • 0 = No OD Temp
  • 1 = OD Temp Display
25 Not Used Not Used
26 Not Used Not Used
27 Not Used Not Used
28 Not Used Not Used
29 Not Used Not Used
30 Deadband
  • 3-10
31 Not Used Not Used
32 Not Used Not Used
33 Compressor Delay
  • 0-5
34 Temp Stop - Heat
  • 40-90
35 Temp Stop - Cool
  • 45-99
36 Not Used Not Used
37 Temp Adjustment
  • -3 to +3
43 Filter Timer
  • 0 = Off
  • 1 = 10 Days
  • 3 = 60 Days
  • 4 = 120 Days
44 Humidifier Pad Monitor
  • 1 = 90 Days
  • 2 = 180 Days
  • 3 = 365 Days
45 UV Lamp Monitor
  • 0 = Off
  • 1 = 365 Days