Knowledgebase

Superheat Chart - Non-Expansion Valve

Article ID: 303
Last updated: 30 Jun, 2017

"NON-EXPANSION VALVE"

SUPERHEAT CHART

Return Air WB Outdoor Air DB Temp
55 60 65 70 75 80 85 90 95 100 105 110 115
76 45 43 41 39 37 33 31 29 27 27 26 25 23
74 42 40 38 36 34 30 27 25 23 23 22 20 18
72 40 38 36 33 30 26 24 22 20 20 17 15 14
70 37 35 33 30 28 22 20 18 15 15 13 11 8
68 35 33 30 27 24 19 16 14 12 12 9 6
66 32 30 27 24 21 15 13 10 8 8 5
64 29 27 24 21 18 11 9 6
62 26 24 21 19 15 8 5
60 23 21 19 16 12
58 20 18 16 13 8
56 17 15 13 10 5
54 14 12 10 7
52 12 10 3
50 9 7