York Heat Pump: YEE
Re: Lockout Codes / Fault Codes
The control shall provide fault codes using the Status LED. The table below describes the LED displays during fault codes.
The "lockout" can be Reset by: 1) cycling power to the air handler or 2) turning the thermostat system switch "Off" and then back to "On".
LOCKOUT CODES:
| Flashes | Description |
| 2 | Hi pressure fault (not in lockout yet) |
| 3 | Hi pressure lockout (last mode was compressor) |
| 4 | Hi pressure lockout (last mode defrost) |
| 5 | Low pressure lockout (last mode compressor) |
| 6 | Low voltage (< 19.2 volts) |
| 7 | Low voltage (< 16 volts) |
| 8 | Coil sensor failure (open or shorted) |
| 9 | Ambient sensor failure (open or shorted) |
| 10 | Control failure |