M4HP4 - Defrost Problem / Outdoor Coil Frozen

Ameristar Heat Pump: M4HP4

Re: Defrosting Problem / Outdoor Coil Frozen

The M4HP4 uses a "Hybrid" Demand Defrost control board with a timer.

The board uses an Ambient (outdoor) Sensor, a Liquid Line Sensor and an adjustable 30 or 60 min. timer to determine when defrost should occur.


Qty Possible Causes:
Bad Liquid Line Sensor
Bad Defrost Board
Bad Condenser Fan Motor
Mis-Placed Coil Sensor
Bad Fan Capacitor
Low Refrigerant Charge
Bad Expansion Valve
Stuck Contactor


CHECKOUT:

1. Check Contactor 


2. Check Outdoor Fan


3. Test Defrost Cycle


4. Check Liquid Line Sensor


5. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

6. Check Defrost Timer