GSZ14 - Defrost Problem, Outdoor Coil Frozen

Goodman Heat Pump: GSZ14

Re: Defrost Problem, Outdoor Coil Frozen

The Goodman GSZ14 Heat Pump uses a Time & Temperature Defrost Board.

► There are two different defrost boards used on these models. 

Qty Possible Causes:
2 Bad or Disconnected Defrost Stat
Bad Defrost Board
Low Refrigerant Charge
Bad Cond Fan Motor / Capacitor
Mis-Located Defrost Stat
Stuck Reversing Valve
Defrost Timer Set Too Long

CHECKOUT:

1. Check Operating Status


2. Check Fan Motor


3. Check Refrigerant Charge

Hook-up refrigerant gauges to the pressure ports on the unit.

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 70-100 Suction
  • 250-320 Discharge
  • 100-135 Suction
  • 250-375 Discharge

4. Check Defrost Board